EasyManua.ls Logo

DOD CL96 - Page 27

DOD CL96
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 24 of 44
DOD Technologies, INC • 675 Industrial Dr. Bldg. A • Cary, IL 60013 • Phone (815) 788-5200 • Fax (815) 788-5300
DC-MAN-CL96Servicemanual
Innovative Life Safety Systems & Services
For the optic system to communicate properly the addresses on each block must be set correctly. A 32
point analyzer should be addressed 1 through 8 and a 16 point analyzer should be addressed 1 through
4. Using the optic block map on each analyzer and the chart below, with the optic covers removed,
confirm the addresses are correct.
Points
Binary
Address
1 through 4
1
5 through 8
2
9 through 12
3
13 through 16
4
17 through 20
5
21 through 24
6
25 through 28
7
29 through 32
8
After the addresses are verified check to confirm the analyzer communication cable is connected
properly at the PC (see image below). Then confirm all optic block communication cables are securely
connected to the interconnect board below the analyzer (see image below).