EasyManua.ls Logo

DOD CL96 - Optic Cleaning Procedure

DOD CL96
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 16 of 44
DOD Technologies, INC • 675 Industrial Dr. Bldg. A • Cary, IL 60013 • Phone (815) 788-5200 • Fax (815) 788-5300
DC-MAN-CL96Servicemanual
Innovative Life Safety Systems & Services
96156
New Logging Span
New Logging Span
None needed
96157
Data Logging Cleanup
Data Logging Cleanup
None needed
96158
New Logging Disk Setup
New Logging Disk Setup
None needed
96159
Gate Open Verification
System had to retry gate open process.
Refer to the Gate
Fault Procedure
96160
Gate Close Verification
System had to retry Gate close process.
Refer to the Gate
Fault Procedure
96161
Factory Log->
Factory Log mode enabled
None needed
96162
PLC:
PLC: message
None needed
96162
Output testing
Output testing was done
None needed
96162
Temperature Validation
Temperature Validation
None needed
Optic Cleaning Procedure:
This procedure should be followed when any of the following messages appear in the CL96 event log:
1. Optic Calibration Required (service fault)
2. Optic point needs cleaning
3. Optic adjustment suggested
The events above may appear in the event log if there is an issue with the optic system. The optic
system is self-adjusting and will make the required adjustments internally when one of the channels
becomes dirty until further action is necessary. If the Optic Calibration Service Fault appears the system
can no longer compensate for the dirty optic channels and the following procedure must be followed:
First enter the System screen by following the steps below:
1. Enter Setup Menu
2. Enter Factory Menu
3. Enter password 1225
4. Select the System tab
5. Press the DAC button for any active analyzer ( see image below )