DOD Technologies, INC • 675 Industrial Dr. Bldg. A • Cary, IL 60013 • Phone (815) 788-5200 • Fax (815) 788-5300
Innovative Life Safety Systems & Services
The PC cannot communicate with the
I/O modules
1. Refer to the I/O
Verification
Procedure
Point Disabled Due to High
Background
A point has been disabled due to a high
background
1. Press Verify Optics
button in the Load
Tape screen
Warning: PT Disabled, Check
Optic Block(Ref)
A point was disabled due to reference
fluctuations
1. Replace the optic
block
Pyrolyzer Failure - Point Disabled
A single Pyrolyzer element has failed
No event file found for selected
date
The CL96 could not locate a log file for
the selected day.
Faults and alarms were reset.
Optic calibration was manually
performed.
Flow offset calibration was performed.
Point configuration
updated/saved
Point Configuration was changed and
saved.
Machine configuration
updated/saved
System Configuration was changed and
saved.
Multi-Point configuration change
Multi-Point configuration change.
Previous machine settings
restored.
Previous machine settings restored.
ChemLogic tape days counter
reset
ChemLogic tape days counter reset.
Optic Point Needs Cleaning
Optic Point Needs Cleaning
1. Refer to the Optic
Cleaning Procedure.
Optic Adjustment Suggested
Optic Adjustment Suggested
1. Refer to the Optic
Cleaning Procedure.
Point Alarm Output Disable
Point Alarm Output Disable
Point Output Disable Timer
Reset
Point Output Disable Timer Reset
A point has an unstable reference value.
Established PLC Connection
Established PLC Connection
Restarting PLC Connection
Restarting PLC Connection