Doc. No.: M1500, Rev. 6
Page 22 of 127
67733 Gross Point Road 900 Santa Fe Dr.
1.11 Conduit
All probe and sensor cabling to the SiteSentinel iTouch Controller must be in rigid steel conduit. The conduit
must be dedicated to intrinsically safe wiring for this Controller.
Probe and sensor wiring for this Controller can share the same conduit.
This Controller’s intrinsically safe wiring cannot share the same conduit with other equipment’s intrinsically safe
wiring.
NOTE: PVC conduit may be substituted for rigid steel conduit where acceptable by local codes. Use
SHIELDED cable for sensor and probe wiring as described in the above sections.
The size and number of probe and sensor conduits (probe-sensor-to-controller) depends on how many probes
and sensors your site has.
It is recommended to group probe wires into separate conduits for each SiteSentinel iTouch Controller I.S.
Interface Module position.
Probe Quantity vs. Conduit Capacity
Number of Probes
Number & Size of Conduits
1 to 2
One 13 mm (0.5 in)
3 to 4
One 19 mm (0.75 in)
5 to 6
One 13 mm (0.5 in) and one 19 mm (0.75 in)
7 to 8
Two 19 mm (0.75 in)
9 to 12
Three 19 mm (0.75 in)
13 to 16
Four 19 mm (0.75 in)