14.1.6 Installing the 30-3222
See the Local and National Electrical Codes for your location. Make sure that the
cabling leading back to the controller (gas/oil resistant Petro Vend number 12-
1030) is installed in conduit dedicated to intrinsically safe wiring.
NOTE: When installing, avoid any immersion in liquid (either hydrocarbon or water). Immersion shortens the
sensor’s life. Immersion may also prevent the sensor from working properly.
This sensor requires one (1) Controller Interface Module position
Review the Connections table and the Typical Installation drawing below
Use the supplied cable gland and silicon wire nuts
Install seal-offs at both ends of the conduit run
30-3222 Connections
I.S. Interface Module Position 1 Terminals
Sensor Wire
+12 (Power)
Red
(Signal)
Black
(Ground)
No Connection
Figure 14-3 Hydrocarbon Vapor Sensor Installation