Doc. No.: M1500, Rev. 6
Page 62 of 127
• 67733 Gross Point Road 900 Santa Fe Dr.
14.1.6 Installing the 30-3222
See the Local and National Electrical Codes for your location. Make sure that the
cabling leading back to the controller (gas/oil resistant Petro Vend number 12-
1030) is installed in conduit dedicated to intrinsically safe wiring.
NOTE: When installing, avoid any immersion in liquid (either hydrocarbon or water). Immersion shortens the
sensor’s life. Immersion may also prevent the sensor from working properly.
• This sensor requires one (1) Controller Interface Module position
• Review the Connections table and the Typical Installation drawing below
• Use the supplied cable gland and silicon wire nuts
• Install seal-offs at both ends of the conduit run
I.S. Interface Module Position 1 Terminals
Figure 14-3 Hydrocarbon Vapor Sensor Installation