14.1.9 Installing the 30-3223
See the Local and National Electrical Codes for your location. Make sure that the
cabling leading back to the controller (gas/oil resistant Petro Vend number 12-
1030) is installed in conduit dedicated to intrinsically safe wiring.
• This sensor requires one (1) Controller Interface Module position
• Review the Connections table and the Typical Installation drawing below
• Use the supplied cable gland and silicon wire nuts
• Install seal-offs at both ends of the conduit run
I.S. Interface Module Position 1 Terminals
Figure 14-4 Interstitial Optical Liquid Sensor Installation
14.1.10 Controller Setup for Interstitial Optical Liquid Sensor
1. Configure the barrier position to be a generic sensor (or, if using SiteConnect choose the appropriate
icon) and install that position.