Appendix B – Alarm Kit Option
Alarm Kit Part Numbers
• 30-2015 (115 VAC)
• 30-2015-230 (230 VAC)
The Alarm Box requires mains/line voltage. Obtain power from the distribution panel and run the wiring through
steel conduit. Use 14-gauge gas and oil resistant cable.
The Alarm Box requires an external relay. This relay is not s supplied with the Alarm Kit – obtain a relay with
the specifications given in the table below.
External Alarm Relay Specifications (NOT Supplied)
12 VDC @ less than 100 mA
115 or 230 VAC @ greater than 500 mA
Installation
1. Install the relay in an external 4” x 4” electrical box or other suitable enclosure.
2. Run rigid conduit from the SiteSentinel iTouch Controller to the relay enclosure.
3. Run the same kind of conduit from the relay enclosure to the Alarm Box.
The Alarm Box will sound its horn and illuminate its light when the contacts close in the SiteSentinel iTouch
Controller.
Press the SILENCE button on the Alarm Box to silence the horn. The Alarm Box light, however, remains
illuminated for as log as the contacts in SiteSentinel iTouch Controller are closed or the switch is pressed.
Attach a switch across position 1 and 2 (see the illustration above) to energize or de-energize an external relay.