12.1.1 Installing the 30-3219-12
See the Local and National Electrical Codes for your location. Make sure that
the cabling leading back to the controller (gas/oil resistant Petro Vend number
12-1030) is installed in conduit dedicated to intrinsically safe wiring.
NOTE: Hydrocarbons (i.e., gasoline, diesel and jet fuel, etc.) float on water. If this sensor is fully submerged
in water, the polymer will NOT detect hydrocarbon liquid.
This sensor requires one (1) Controller Interface Module position
Review the Connections table and the Typical Installation drawing below
Use the supplied cable gland and silicon wire nuts
Install seal-offs at both ends of the conduit run
Connections
I.S. Interface Module Position 1 Terminals
Sensor Wire
+12 (Power)
Red
Black
Black
(Ground)
No Connection
Figure 12-1 Hydrocarbon Liquid Sump Sensor Installation