EasyManua.ls Logo

Dover OPW SiteSentinel iTouch M1500 - Installing the 30-3207

Dover OPW SiteSentinel iTouch M1500
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. No.: M1500, Rev. 6
Page 43 of 127
67733 Gross Point Road 900 Santa Fe Dr.
11.1.4 Installing the 30-3207
See the Local and National Electrical Codes for your location. Make sure that
the cabling leading back to the controller (gas/oil resistant Petro Vend number
12-1030) is installed in conduit dedicated to intrinsically safe wiring.
NOTE: Hydrocarbons (i.e., gasoline, diesel and jet fuel, etc.) float on water. If this sensor is fully submerged
in water, the polymer will NOT detect hydrocarbon liquid.
This sensor requires one (1) Controller Interface Module position
Review the Connections table and the Typical Installation drawing below
Use the supplied cable gland and silicon wire nuts
Install seal-offs at both ends of the conduit run
30-3207 Connections
I.S. Interface Module Position 1 Terminals
Sensor Wire
+12 (Power)
Red
(Signal)
Black
(Ground)
White (no connection)
Figure 11-4 Typical Installation

Table of Contents

Related product manuals