See the Local and National Electrical Codes for your location. Make sure that
the cabling leading back to the controller (gas/oil resistant Petro Vend number
12-1030) is installed in conduit dedicated to intrinsically safe wiring.
NOTE: Hydrocarbons (i.e., gasoline, diesel and jet fuel, etc.) float on water. If this sensor is fully submerged
in water, the polymer will NOT detect hydrocarbon liquid.
• This sensor requires two (2) Controller Interface Module positions
• Review the Connections table and the Typical Installation drawing below
• Use the supplied cable gland and silicon wire nuts
• Install seal-offs at both ends of the conduit run