30-3224 Connections
I.S. Interface Module Position 1 Terminals
Sensor Wire
+12 (Power)
Red (joined 30-3219-12 and 30-3221-1A red
leads, in junction box).
(Signal)
Black (from Hydrocarbon Sensor)
(Ground)
No Connection
I.S. Interface Module Position 2 Terminals
Sensor Wire
12 (Power)
No Connection
(Signal)
White (from Liquid Level Sensor)
(Ground)
No Connection
Figure 14-5 Combo Single-Level & Hydrocarbon Liquid Sensor Installation
1
st
Barrier Position (Float Sensor)
1. Configure the barrier position to be a sensor (or, if using Site Connect chose the appropriate icon) and
install that position.
2. Set the lower alarm threshold to 2.5 volts.
3. Set the upper alarm threshold to 5.0 volts (disables upper threshold).
o If monitoring a normally wet well, the lower threshold will indicate that the liquid is too low.
o If monitoring a normally dry well, the lower threshold indicates that liquid is too high.