Figure 14-5 Combo Single-Level & Hydrocarbon Liquid Sensor Installation
1
st
Barrier Position (Float Sensor)
1. Configure the barrier position to be a sensor (or, if using Site Connect chose the appropriate icon) and
install that position.
2. Set the lower alarm threshold to 2.5 volts.
3. Set the upper alarm threshold to 5.0 volts (disables upper threshold).
o If monitoring a normally wet well, the lower threshold will indicate that the liquid is too low.
o If monitoring a normally dry well, the lower threshold indicates that liquid is too high.