EasyManua.ls Logo

DSC PC1832 - Function Key Programming; Confirming Module Supervision; Removing Modules; Zone Wiring

DSC PC1832
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
1st digit - enter 0 for Global operation, or enter 1-8 for
Partitions 1-8
2nd digit - enter 1 to 8 for Slot Assignment
5. Press the [#] key twice to exit programming.
6. Continue this procedure at each keypad until all have been
assigned to the correct slot and partition (see section [902].
NOTE:
All keypad assignments must be done at each keypad on
the system. When using LCD keypads, one keypad must remain in
slot 8 to upload/download LCD information. Do not assign more
than one keypad to the same slot.
NOTE: The following keypad versions can only be used on Parti-
tion 1 & 2, and the first 8, 16, or 32 zones: PC5508(Z), PC5516(Z),
PC5532(Z) versions v2.0 & lower, LCD5500(Z) versions 3.x and
lower. To assign a keypad to a slot and select the partition it will
operate in, enter the following:
Function Key Programming
Each of the 5 function keys on each keypad may be programmed
for different operations.
1. Enter Installer Programming.
2. Press [000] for Keypad Programming.
3. Enter [1] to [5] to select function key to program.
4. Enter a 2-digit number for function key option - [00] - [32].
5. Continue from step 3 until all function keys are programmed.
6. Press [#] key twice to exit Installer Programming.
For details on the operation of Function Keys, see section 4.3
’Function Keys.
2.8 Confirming Module Supervision
By default, all modules are supervised upon installation. Supervi-
sion is enabled at all times so the panel can indicate a trouble if a
module is removed from the system. To check which modules are
currently connected and supervised:
1. Press [*][8][Installer Code] to enter Installer Programming.
2. Press [903] to display Module Supervision Field.
3. On an LCD keypad, use the arrow keys to scroll through the
modules the panel has found on the system.
On LED/ICON keypads, zone lights will be turned on accord-
ing to what modules the panel has found on the system.
Refer to the following chart:
If a module is connected but does not show as being present, it
may be due to any of the following reasons:
it is not connected to the Keybus
there is a Keybus wiring problem
the module is more than 1,000'/305m from the panel
the module does not have enough power
the wireless receiver does not have any devices added
NOTE:
Module supervision will not display correctly at an
LCD5500Z v2.x and lower keypad.
2.9 Removing Modules
If a module is no longer required on the system, the panel must
be told to stop supervising the module. To do this:
1. Power down the panel by removing the backup battery and
AC.
2. Remove the module from the Keybus.
3. Power up the panel by connecting the backup battery and
AC.
4. Press [*][8][Installer Code] to enter Installer Programming.
5. Press [902] to enable supervision. The panel will automati-
cally search for all modules connected to the system for the
next 60 seconds. Do not perform any other operations during
this 60 second period.
6. Once the search is complete enter section [903] to confirm
the correct modules are supervised on the system.
2.10 Zone Wiring
For a complete description of the operation of all zone types, see
section 5.2 ’Basic Programming’section [001]-[004].
The panel can be programmed to supervise normally closed, End
of Line, or Double End of Line loops. Refer to the following sec-
tions to study each type of individually supervised zone wiring.
NOTE:
Any zone programmed for Fire or 24-hr Supervisory must
be wired with a single end-of-line (EOL) resistor regardless of the
type of zone wiring supervision selected for the panel (section
[013], options [1], [2]). See Zone Definitions [001]-[004]. If you
change the zone supervision options from DEOL to EOL or from
NC to DEOL (section [013], options [1] or [2]), power the system
down completely, then power it back up for correct operation.
NOTE: For UL Listed Installations use SEOL or DEOL only.
NOTE: Use minimum 22 AWG wire, maximum 18 AWG wire.
NOTE: Do not use shielded wire.
NOTE: Wire run resistance shall not exceed 100Ω.
Burglary Zone Wiring Chart
Normally Closed (NC) Loops
To enable normally closed loops, program section [013], option
[1] to ON.
NOTE:
Do not use Normally Closed Loops for UL Installations.
The following chart shows zone status under certain conditions
for NC Loops:
Keypad Function Keys
[00] - Null [10] - Alarm Memory [24] - Bypass Group Recall
[01] - Partition 1 Select [11] - User Programming [26] - Time & Date Program
[02] - Partition 2 Select [12] - User Functions [27] - Partition 3 Select
[03] - Stay Arm [13] - Command Output 1 [28] - Partition 4 Select
[04] - Away Arm [14] - Command Output 2 [29] - Partition 5 Select
[05] - No Entry Arm [16] - Quick Exit [30] - Partition 6 Select
[06] - Chime On/Off [17] - Activate Stay/Away [31] - Partition 7 Select
[07] - System Test [19] - Command Output 3 [32] - Partition 8 Select
[08] - Bypass Mode [21] - Command Output 4
[09] - Trouble Display [23] - Bypass Recall
Light Module/Device Light Module/Device
[1] Keypad 1 [16] Zones 57 to 64
[2] Keypad 2 [17] Wireless Receiver
[3] Keypad 3 [18] PC5208
[4] Keypad 4 [19] PC5204
[5] Keypad 5 [20] PC5400
[6] Keypad 6 [21] PC59XX
[7] Keypad 7 [22] Alternate Communicator
[8] Keypad 8 [23] Future Use
[9] Zones 9 to 16 [24] Escort5580(TC)
[10] Zones 17 to 24 [25] Future Use
[11] Zones 25 to 32 [26] PC520X-1
[12] Zones 33 to 40 [27] PC520X-2
[13] Zones 41 to 48 [28] PC520X-3
[14] Zones 49 to 56 [29] PC520X-4
[15] PC5100
Wire Gauge Maximum Wire length to End of Line Resistor
24 1900 feet / 579 meters
22 3000 feet / 914 meters
20 4900 feet / 1493 meters
19 6200 feet / 1889 meters
18 7800 feet / 2377 meters
Loop Resistance Loop Status
0Ω (shorted wire, loop shorted) Secure
Infinite (broken wire, loop open) Violated
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL

Table of Contents

Other manuals for DSC PC1832

Related product manuals