38
Fire Zone Trouble (Zones 1-64)
Battery Trouble (PC1616/PC1832/PC1864, PC520X)
Fire Zone Alarm (Zones 1-64, Two-Wire Smoke
Aux Trouble (PC1616/PC1832/PC1864)
Fire Trouble (Two-Wire Smoke)
Bell Trouble (PC1616/PC1832/PC1864)
Fire Tamper/Low Sensitivity (WLS/AML Zones 1-32)
Module Supervisory
Fire Zones Bypassed (Zones 1-64)
Ground Fault (PC5700)
Fire Supervisory (Wireless/AML Zones 1-32)
TLM Trouble (PC1616/PC1832/PC1864, PC5700 Line 1-2)
AC Trouble (PC1616/PC1832/PC1864, PC520X)
FTC Trouble
Periodic Test Transmission: the Periodic Test Transmission
Reporting Code will be transmitted at the specified time, (pro-
grammed in Section 378) every X number of days (see Section
377).
System Test: the System Test reporting code will be transmitted
when a system test is performed on the panel.
[349] - PC5700 Maintenance Reporting Codes
PC5700 Ground Fault Trouble: the panel will transmit this report-
ing code when a Ground Fault Trouble occurs on the PC5700.
PC5700 Ground Fault Restore: the panel will transmit this report-
ing code when the Ground Fault Trouble condition has restored
on the PC5700.
PC5700 TLM 1(2) Trouble: the panel will transmit this reporting
code when a TLM Trouble occurs on the PC5700 Line 1 and/or on
line 2.
PC5700 TLM 1(2) Restore: the panel will transmit this reporting
code when a TLM Restore occurs on the PC5700 Line 1 and/or
Line 2.
[350] - Communicator Format Options
This section requires 2 two digit entries to set the communications
format that is to be used for each phone number (1 per phone
number). The 3rd telephone number uses the format pro-
grammed for the 1st telephone number.
Reporting Codes
SIA -0 is valid in Account or Rep Code (not 00 in a Report-
ing code though)
ADEMCO Contact ID - 0 is not valid in Account or Rep
Code (A must be used, 10 in checksum)
BPS Formats - 0 is not valid in Account or Rep Code (A
must be used)
SIA - This format uses 300 Baud FSK as the communica-
tion media. The Account Code can be 4 or 6 hexadecimal
digits in length, All reporting codes must be 2 digits in
length. The SIA format will transmit a 4 (or 6) digit account
code, a 2 digit identifier code and a 2 digit reporting code.
The 2 digit identifier is pre programmed by the panel.
Contact ID
Contact ID is a specialized format that will communicate informa-
tion quickly using tones rather than pulses. In addition to sending
information more quickly the format also allows more information
to be sent. For example, rather than reporting an alarm zone 1 the
Contact ID format can also report the type of alarm, such as
Entry/Exit alarm zone 1.
If Contact ID Sends Automatic Reporting Codes is selected,
the panel will automatically generate a reporting code for each
event. These identifiers are listed in Appendix A. If the Automatic
Contact ID option is not selected, reporting codes must be pro-
grammed. The 2-digit entry determines the type of alarm. The
panel will automatically generate all other information, including
the zone number.
NOTE:
If the Automatic Contact ID option is selected, the panel
will automatically generate all zone and access code numbers,
eliminating the need to program these items.
NOTE: The zone number for Zone Low Battery and Zone Fault
events will not be identified when Programmed Contact ID is used.
If the Contact ID uses Automatic Reporting Codes option is
enabled, the panel will operate as follows:
If an event’s reporting code is programmed as [00], the
panel will not attempt to call the central station.
If the reporting code for an event is programmed as any-
thing from [01] to [FF], the panel will automatically generate
the zone or access code number. See Appendix A for a list
of the codes which will be transmitted.
If the Contact ID uses Programmed Reporting Codes option
is enabled, the panel will operate as follows:
If an event’s reporting code is programmed as [00] or [FF],
the panel will not attempt to call central station.
If the reporting code for an event is programmed as any-
thing from [01] to [FE], the panel will send the programmed
reporting code.
Account numbers must be four digits.
If the digit ‘0’ is in the account number substitute the HEX
digit ‘A’ for the ‘0’.
All reporting codes must be two digits.
If the digit ‘0’ is in the reporting code substitute the HEX
digit ‘A’ for the ‘0’.
To prevent the panel from reporting an event program the
reporting code for the event as [00] or [FF].
NOTE:
This communication format cannot be selected if Down-
look is required.
Contact ID Sends Automatic
Reporting Codes . . . . . . . . . . . . . . . . . . . Section [381], Option [7]
SIA (Level 2)
SIA is a specialized format that will communicate information
quickly using frequency shift keying (FSK) rather than pulses. The
SIA format will automatically generate the type of signal being
transmitted, such as Burglary, Fire, Panic etc. The two digit
reporting code is used to identify the zone or access code num-
ber.
NOTE:
SIA format must be used if Downlook is required.
If the SIA format is selected the panel can be programmed to
automatically generate all zone and access code numbers elimi-
nating the need to program these items.
If the SIA Sends Automatic Reporting Codes option is enabled
the panel will operate as follows:
1. If the reporting code for an event is programmed as [00] the
panel will not attempt to call the central station.
2. If the reporting code for an event is programmed as anything
from [01] to [FF] the panel will AUTOMATICALLY generate
the zone or access code number.
3. Bypassed zones will always be identified when partial clos-
ing the system.
Entry Communication Format
01 20 BPS, 1400 HZ handshake
02 20 BPS, 2300 HZ handshake
03 DTMF CONTACT I.D.
04 SIA FSK
05 Pager
06 Residential Dial
07 10 BPS, 1400 Hz handshake
08 10 BPS, 2300 Hz handshake
09 Private Line
10 Scantronics 4-8-1 Fast Slot
11 For Future Use
12 Robofon
13 CESA 200