7.1 UL Listed Commercial and Residential Installations
The installation requirements listed below must be met for the following grades of
service.
Grade AA Central Station and Police Connect (Standard or
Encrypted Line Security Service)
The installation must use T-Link module which communicates
over LAN/WAN to the Sur-Gard MLR-IP receiver or the TL250
which communicates over LAN/WAN/Internet to the SG System
III receiver. Polling time must be 90 seconds. Compromise detec-
tion time must be 6 minutes.
Grade A Local
The installation must have a bell which is UL Listed for
mercantile local alarms (AMSECO MBL10B with model
AB-12 bell housing).
The digital communicator must be enabled.
The control panel must be in the attack-resistant enclosure
(DSC Model CMC-1 or PC4050CAR).
Grade B Central Station and Police Connect
The installation must have a bell which is UL Listed for
mercantile local alarms (AMSECO MBL10B with model
AB-12 bell housing).
The digital communicator must be enabled.
The control panel must be in the attack resistant enclosure
(DSC Model CMC-1 or PC4050CAR).
Grade C Central Station
The digital communicator must be enabled.
The control panel must be in the attack resistant enclosure
(DSC Model CMC-1 or PC4050CAR).
All Commercial Installations
The Entry Delay must not exceed 120 seconds
The Exit Delay must not exceed 120 seconds.
The minimum Bell Time-out is 15 minutes.
Residential Fire & Burglary Installations
The Entry Delay must not exceed 45 seconds
The Exit Delay must not exceed 60 seconds.
The minimum Bell Time-out is 4 minutes.
Home Health Care Signaling Equipment
There must be at least two keypads, one of either the
LCD5500Z/LCD5520Z or LCD5501Z and one of the follow-
ing models, PC5508Z, PC5516Z or PC5532Z.
Each system shall be programmed to activate an audible
Trouble signal within 90 seconds upon loss of microproces-
sor memory.
The minimum Bell Time-out is 5 minutes.
Programming
The notes in the programming sections describing the system
configurations for UL Listed installations must be implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area is to
be under the responsibility of one ownership and management
(i.e., one business under one name). This may be a group of
buildings attached or unattached with different addresses but
under the responsibility of someone having mutual interest. The
person of mutual interest is not the alarm-installing company.
Bell Location
The alarm sounding device (bell) must be located where it can be
heard by the person or persons responsible for maintaining the
security system during the daily arming cycle.
Protection of the Control Unit
The local control and the local power supply must be protected in
one of the following ways:
The control unit and audible alarm device must be in a pro-
tected area which is armed 24 hours a day.
Each partition must arm the area protecting the control unit
and the audible alarm device power supply. This may
require duplicate protection armed by each partition.
Access to this protected area, without causing an alarm,
will require that all partitions be disarmed.
In all cases described above, the protected area for the
control unit must be programmed as not-bypassable.
Casual Users
The installer should caution the user(s) not to give system infor-
mation to casual users (e.g. codes, bypass methods, etc. to baby-
sitters or service people). Only the One-Time Use codes should
be given to casual users.
User Information
The installer should advise the users and note in the User’s
Manual:
Service organization name and telephone number
The programmed exit time
The programmed entry time
Test system weekly
Two-Wire Smoke Detector Compatibility (if available)
Maximum loop resistance: 24 Ohms
Operating Voltage Range: 9.8 - 13.8 V
DC
Maximum Alarm Current: 89 mA
Compatibility Identifier: PC18-1
See
Section 5
PGM Wiring
for compatible 2-wire smoke detectors.
SIA FAR Installations
Minimum requirement system for SIA-FAR Installations:
1 PC1616/PC1832/PC1864 Control panel
1 Local annunciation device
The local annunciation devices may be any combination of the
following keypads, as long as there is at least one LCD keypad in
the installation (Model LCD5500Z or PK5500).
LCD5500Z LCD5501Z PK5500 PK5508
PKP-LCD PKP-ICN PK5501 PK5516
The following optional subassembly modules also bear the SIA
FAR classification and may be used if desired:
PC5108 Zone Expander Module
Compatible initiating devices: Bravo200 series, 300 series, 400
series, 500 series, 600 series, AC-100, Encore300 series,
Force200 series, 210 series, MN240.
PC5208 Low Current PGM Output Module
The following optional accessory modules also bear the SIA FAR
classification and may be used if desired.
PC5204 Auxiliary Power Supply with PGM output ports
Escort5580/Escort5580TC, PC5400 Printer Module
Caution
For SIA FAR installations, only use modules / devices that
are listed on this page.
Fire Alarm Verification feature (Auto Verified Fire zone) is
not supported on 2-wire smoke detectors zones. This fea-
ture may be enabled for 4-wire smoke detectors only.
Call Waiting Cancel (Section 382 Option 4) feature on a
non-Call Waiting line will prevent successful communica-
tion to the central station.
All smoke detectors on the system must be tested annually
by conducting the Installer Walk Test prior to exiting the
walk test mode, a sensor reset must be conducted on the
system, [
,][7][2] to reset all latching 4-wire smoke detec-
tors. Please refer to the smoke detector installation instruc-
tions on how to correctly test the detectors.