5
The following section provides a description of how to wire and
configure devices and zones.
2.1 Installation Steps
The following steps are provided to assist with the installation of
the panel. It is suggested that you read over this section briefly to
get an overall understanding of the order of installation. Once this
is done carefully work through each step. Working from this plan
will help reduce problems and reduce the overall installation time
required.
Step 1 Create a Layout
Draw a rough sketch of the building and include all alarm detec-
tion devices, zone expanders, keypads and all other modules that
are required.
Step 2 Mounting the Panel
Locate the panel in a dry area, preferably located near an
unswitched AC power source and the incoming telephone line.
Before attaching the cabinet to the wall be sure to press the five
circuit board mounting studs into the cabinet from the back.
NOTE:
Complete all wiring before applying AC or connecting the
battery.
Step 3 Wiring the Keybus
Wire the Keybus to each of the modules following the guidelines
provided in Section 2.4.
Step 4 Assigning Zones to Zone Expanders
If zone expander modules are being used the modules must be
configured so the panel knows which zones are assigned to each
expander. Follow the guideline provided in Section 2.6 to assign
zones to expanders.
Step 5 Zone Wiring
Power down the control panel and complete all zone wiring. Fol-
low the guidelines provided in section 2.10 to connect zones
using normally closed loops, single EOL resistor, double EOL
resistors, Fire zones and Keyswitch Arming zones.
Step 6 Completing Wiring
Complete all other wiring including bells or sirens, telephone line
connections, ground connections or any other wiring necessary.
Follow the guidelines provided in section 2.2 “Terminal Descrip-
tions”.
Step 7 Power up the Control Panel
Once all zone and Keybus wiring is complete, power up the con-
trol panel.
NOTE:
The panel will not power up if only the battery is con-
nected.
Step 8 Keypad Assignment
Keypads must be assigned to different slots to be properly super-
vised. Follow the guideline provided in section 2.7 to assign key-
pads.
Step 9 Confirming Module Supervision
By default, all modules are supervised upon installation. Supervi-
sion is enabled at all times so that the panel can indicate a trouble
if a module is removed from the system.
To confirm that each module is properly supervised, follow the
guidelines provided in section 2.8.
Step 10 Programming the System
Section 4.0 provides a complete description of how to program
the panel. Section 5.0 contains complete descriptions of the vari-
ous programmable features, what options are available and how
the options function. The Programming Worksheets should be
filled out completely before attempting to program the system.
Step 11 Testing the System
Test the panel completely to ensure that all features and functions
are operating as programmed.
2.2 Terminal Descriptions
AC Power Terminals
The panel requires a 16.5V, 40VA transformer. Connect the trans-
former to these terminals.
The panel can be programmed to accept a power line frequency
of either 50Hz AC or 60Hz AC in programming section [701],
option [1].
NOTE:
Do not connect the transformer until all other wiring is
complete.
Battery Connection
The battery is used to provide back up power in the event of an
AC power failure and to provide additional current when the panel
demands exceed the power output of the transformer, such as
when the panel is in alarm.
NOTE:
Do not connect battery until all other wiring is complete.
Connect the RED battery lead to the positive of the battery, the
BLACK battery lead to the negative.
The High Current Charge/Standard Battery Charge option
(section [701], option [7]) allows you to choose between a high
current battery charge and the standard battery charge rate.
High Current/Standard Battery Charge . . . . . . . . .Section [701]: [7]
Auxiliary Power Terminals - AUX+ and GND
These terminals provide up to 500mA of current at 12 V
DC
(700mA of current at 12VDC for UL/ULC) (550mA of current at
12V
DC for IMQ) for devices requiring power (rated 11.6-12.6 VDC
for UL residential applications). Connect the positive side of
any device requiring power to the AUX+ terminal, the negative
side to GND. The AUX output is protected; if too much current is
drawn from these terminals (wiring short) the panel will tempo-
rarily shut off the output, until the problem is corrected.
NOTE:
When using a 12V 14Ah battery, the maximum AUX capac-
ity for 24-hour standby is 470mA.
Bell Output Terminals - BELL+ and BELL-
These terminals provide up to 2A of current at 12V
DC (with
standby battery; 700 mA continuous) for powering bells, sirens,
strobes or other warning type equipment. Connect the positive
side of any alarm warning device to BELL+, the negative side to
BELL–. The BELL output is protected; if too much current is
drawn from these terminals (wiring short) the BELL PTC will open.
The Bell output is supervised. If no alarm warning device is being
used connect a 1K
Ω resistor across BELL+ and BELL– to prevent
the panel from displaying a Bell Trouble condition.
NOTE:
The Bell output is current limited with a 2A PTC.
NOTE: Steady, Pulsed and Temporal Three Pattern alarms are sup-
ported.
Keybus Terminals - RED, BLK, YEL, GRN
The Keybus is used by the panel to communicate with modules
and by modules to communicate with the panel. Each module has
four Keybus terminals that must be connected to the four Keybus
terminals on the panel.
Section 2: Installation and Wiring