31
4 Remote Reset ON Remote Reset Enabled. The purpose of this feature is to force the end user to contact the Installer/Cen-
tral Station whenever they have an alarm condition. This is accomplished by locking out the panel after an
alarm occurs, which will force the end user to call the Installer/Central Station to get a Reset code which
must be entered on the keypad before they will be able to use their system.
In the Armed state, when an Alarm occurs on a burglary zone (please refer to chart below), the system will
be locked out after disarming the panel. The panel will remain locked until a 4 digit Reset code that is pro-
vided by the Installer/Central Station is entered on a keypad. If the Duress code is used to disarm the parti-
tion, then the system will not be locked out. In the Disarmed state, only Audible 24Hr Burglary zones,
Audible 24Hr Latching Tamper zones, and Audible 24Hr zone on PGM 2 will cause the panel to be locked
out. To get the Reset code from the Installer/Central Station, the end user must provide the Installer/Central
Station with the corresponding System Lock code, displayed on the keypad.
The System Lock code will be randomly generated and displayed on the keypad after an alarm condition
when one of the following conditions occurs:
the system has been disarmed (Duress Code excluded)
the bell has timed out (24Hr zones - please see chart below)
an access code has been entered (24Hr zones - please see chart below)
On a LCD keypad, the message “REMOTE RESET RQD” will be displayed on the top line and “CODE” along
with the actually code will be displayed across the bottom line.
On an LED keypad, the reset number will be scrolled across the keypad. Each digit will be displayed one at
a time for 1 second with a pause of 1 second between digits. There will be a 3 second pause after the last
digit of the System Lock code before the System Lock code is repeated. This routine will continue until the
Unlock code (from Installer/Central Station) is entered.
NOTE: While the system is locked out, the only options available are [*][3], [*][6], [*][7], and
[*][8]. Going into [*][8] Installers Programming while the panel is locked out will unlock the
panel. The system will continue to function properly (alarms, tampers, etc) while the system is
locked out. This feature will follow the Keypad Lockout . If the Duress Code is used to disarm
the system, the system will not be locked out. Silent 24Hr zone on PGM 2 will not Lock out the
panel. Lock out will follow both the Transmission and Bell Delays.
OFF Remote Reset Disabled The system will not be locked out after an alarm occurs.
5 Engineer’s Reset ON Engineer’s Reset Enabled If the panel has gone into alarm during the previous armed period, or if a 24
Hour alarm has occurred (armed or disarmed), the system will not be ready to arm (Ready Light OFF) until
the Installers Programming is entered or Engineer’s Reset is performed via Downloading Software. This fea-
ture applies to Tampers and Faults in both Armed and Disarmed states and does not apply to Module
Tampers, System Supervisories, Zone Expander alarms or PGM2 Input Alarms.
OFF Engineer’s Reset Disabled If the panel has gone into alarm during the previous armed period, or if a 24
Hour alarm has occurred (armed or disarmed), the system will be ready to arm.
6 Disarming (WLS Key) ON Keyswitch Disarming During Entry Delay Only All key-switches and Wireless Keys on the system will
only disarm the panel if an entry delay is active.
OFF No Entry Delay for Keyswitch Disarm All key-switches and Wireless Keys will disarm regardless if entry
delay is active or not.
7Installer Access
Requires DLS win-
dow
ON Installer Access follows DLS window Access to Installers programming requires the DLS window to be
opened up in order to access installers. Enable DLS window by entering [*][6][Access Code][5].
NOTE: For this feature to work section 401 option 2 must be enabled.
OFF Installers can be accessed at any time Installers programming can be accessed at any time.
8 Arming Inhibit ON Arming Inhibit for All Troubles When there is a trouble present on the system arming will be inhibited,
until the trouble is restored.
OFF Troubles do not Inhibit Arming The system can be armed even when there is a trouble present.
Option Definition On/Off Description
UK
* These zones will lock out the system only if the zone is audible.
Zone Definition Armed Disarmed Zone Definition Armed Disarmed
00 Null Zone (Not Used) 20 24 Hour Freeze
01 Delay 1 Lock 21 24 Hour Latching Tamper Lock Lock *
02 Delay 2 Lock 22 Momentary Keyswitch Arm
03 Instant Lock 23 Maintained Keyswitch Arm
04 Interior Lock 24 Not Used
05 Interior Stay/Away Lock 25 Interior Delay Lock
06 Delay Stay/Away Lock 26 24-Hr Non-Alarm
07 Delayed 24-Hr Fire 27 Delayed 24Hr Waterflow
08 Standard 24-Hr Fire 28 Instant Waterflow
09 24-Hr Supervisory Lock 29 Auto Verify Fire
10 24-Hr Supervisory Buzzer 30 Fire Supervisory
11 24-Hr Burg Lock Lock * 31 Day Zone Lock
12 24-Hr Holdup 32 Instant, Stay-Away
13 24-Hr Gas 33 Push to Set Zone
14 24-Hr Heat 34 Final Door Set Lock
15 24-Hr Medical 35 24Hr Bell/Buzzer Lock
16 24-Hr Panic 36 24 Hour Non-Latching Tamper
17 24-Hr Emergency 37 Night Zone Lock
18 24-Hr Sprinkler 87 Delayed 24 Hour Fire (Wireless)
19 24-Hr Waterflow 88 Standard 24 Hour Fire (Wireless)
UK
UK
EN
EN