Chapter 4 Programming Descriptions
21
[380] First Communicator Option Code
[381] Second Communicator Option Code
[382] Third Communicator Option Code
Option Description
[1]
ON:
the system communicator is enabled.
OFF: the communicator is disabled.
[2]
ON:
the system transmits alarm restorals if the zone is restored and the bell has timed out.
OFF: the system transmits alarm restorals immediately when the zone is restored.
[3]
ON:
the panel uses rotary (pulse) dialing. OFF: the panel uses DTMF (touchtone) dialing.
[4]
ON:
the panel will switch from DTMF dialing to rotary dialing after the 4th failed attempt to communicate.
OFF: the panel will use DTMF dialing for all dialing attempts.
[5]
ON:
the system uses the Third Phone Number to back up the First Phone Number.
OFF: the Third Phone Number is disabled.
[6]
ON:
the system alternates between the First Phone Number and Third Phone Number when attempting to report an event.
OFF: the panel will dial the First Phone Number for the programmed number of attempts, then switch to the Third Phone Number.
[7]
For Future Use
[8]
ON:
the Delinquency feature follows zone activity. OFF: the Delinquency feature follows arming.
Option Description
[1]
ON
: the keypad beeps 8 times after successfully transmitting the Opening After Alarm reporting event.
OFF: the keypad does not beep.
[2]
ON
: the bell output squawks 8 times after successfully transmitting the Opening After Alarm reporting event.
OFF: the bell output does not activate.
[3]
ON
: the system uses programmed reporting codes when transmitting using the SIA format.
OFF: the system automatically generates all reporting codes transmitted.
[4]
ON
: the system beeps the keypad 8 times after successfully transmitting a Closing reporting event.
OFF: the keypad does not beep.
[5]
ON
:
the system requests a Listen in/two-way session the next time it calls the 1st/3rd Phone Number when the PC59xx transmits a request
.
OFF: the system ignores the request from the PC59xx.
This option is used with PC59xx series modules.
[6]
ON
: the system requests a Listen in/Two-way session the next time it calls the 2nd Phone Number when the PC59xx transmits a request.
OFF: the system will ignore the request from the PC59xx.
This option is used with PC59xx series modules.
[7]
ON
: the system uses Contact ID format programmed reporting codes when transmitting reporting codes.
OFF: the system automatically generates all reporting codes transmitted.
[8]
ON
: the system will follow ULC Communication Priority.
OFF: the system will follow standard communications priority.
Option Description
[1]
For Future Use
[2]
ON
: the system will transmit all alarms during Walk Test. OFF: the system will not report alarm events during Walk Test.
[3]
ON
: the keypad will display the message ‘Communications Cancelled’ (programmable LCD) or ‘CC’ (fixed-message LCD) upon
successful transmission of the Communication Cancelled reporting event.
OFF: the keypad will not display these messages.
[4]
ON
: the system dials the Call Waiting Cancel String on the first attempt to dial the central station.
OFF: the system does not dial the Call Waiting Cancel String.
[5]
ON
: enables support for the TL/GS Module. OFF: disables TL/GS Module.
[6]
ON
: the AC Failure Transmission Delay Timer is in hours. OFF: the delay is in minutes.
[7]
ON
: sets the number of Dialing attempts to 1 when using Residential Dial Format.
OFF: residential Dial follows Dialing Attempt Counter.
[8]
For Future Use