DSE Model 4110 AutoStart Operators Manual
12 057-022 4110 OPERATING MANUAL ISSUE 5.1 18/06/2007 JR
Function
! 1 ! 2
Value (Default in Bold)
Nominal Frequency
{
O
{ { {
{ { {
50 Hz (O/S +14% /
Overshoot +24%)
{ {
O
60 Hz (O/S +14% /
Overshoot +24%)
The systems nominal frequency. Either 50 Hz or 60 Hz
Nominal DC Voltage
{
O
{ {
O
{ { {
12V DC (CF 8V)
{ {
O
24V DC (CF 16V)
The generator battery voltage. Either 12 Volts or 24 Volts. It is used for the charge alternator failure level.
LOP Switch Contact
{
O
{
O
{
{ { {
Close on Fault
{ {
O
Open on Fault
Configuration for the oil pressure switch. Either to close to battery negative on a fault, or open on a fault.
HET Switch Contact
{
O
{
O O
{ { {
Close on Fault
{ {
O
Open on Fault
Configuration for the coolant temperature switch. Either to close to battery negative on a fault, or open on a fault.
Crank disconnect on
Oil Pressure
{
O O
{ {
{ { {
Disabled
{ {
O
Enabled (2 Second
Delay)
If this is enabled, the starter motor will disconnect 2 seconds after the oil pressure switch detects oil pressure.
NOTE:- Not suitable for all generators, due to the different monitoring points on lubrication systems.
Underspeed
Detection
{
O O
{
O
{ { {
Disabled
{ {
O
Enabled (U/S –20%)
If this is enabled, the unit will shut down the generator if the frequency falls below 20% of the nominal frequency.