19. REV CONTRL REM
Allows the user to switch the controller from forward to reverse in conjunction with TB2-25
being closed to common and “REVERSE CONTROL” being enabled.
• ENABLE
• DISABLE (default)
20. CLOSED LOOP TORQUE
Allows the user to use the setting in Menu A, Parameter 6 (TORQ PULSES/REV) instead of
Menu A, Parameter 5. Note, this must be used in conjunction with TB2-25 being closed to
common.
• ENABLE
• DISABLE (default)
21. CLUTCH CUR SCALE
Used to adjust the difference between the actual clutch current (measured with a DC clamp
on meter) and the current reading of the EC 2000. If the keypad displayed clutch current is
less than measured, increase the percentage, and vice-versa (Default: 100%).
22. CLUTCH PPR SCALE
Used to fine tune the Menu A, Parameter 5 (TACH PULSES/REV) speed feedback rate (Default:
100%). This is typically used for nonstandard or pulse pickup units.
23. TORQ PPR SCALE
Used to fine tune the Menu A, Parameter 6 (TORQ PULSES/REV) alternate feedback rate
(Default: 100%). This is typically used for nonstandard or pulse pickup units.
24. PULSE MAX FREQ
Used to scale the pulse follower input when “PULSE” is selected for “PRESET 1” in Menu K
(SOURCE SELECT). Default: 100.
25. BOOT START DELAY
Delays the boot up sequence of the EC 2000. This is used for more unstable power supplies
(Default: 0 sec).