14. SPEED FILTER AVER
Allows for taking an average of the speed feedback readings. This is primarily used for non-
standard speed feedback configurations, noise affected configurations, or heavy loads not
getting up to speed in a timely manner (Default: 0).
15. SPEED FILTER CLAMP
Limits the amount of speed feedback readings done by the EC 2000. This is primarily used for
non-standard speed feedback configurations, noise affected configurations, or heavy loads
not getting up to speed in a timely manner (Default: 0).
16. MEMORY RESET EN
Allows the user to reset the stored parameters back to the factory defaults upon powering
or resetting the device (pressing the SW1 button on the 15-1200-1 logic board).
• YES
• NO (default)
Note: Parameters can also be reset back to factory defaults by placing a jumper between
terminals 32 and 29 on TB2, while also removing all other connections on TB2.
17. REVERSE SETPOINT
Allows the user to use a setpoint reference signal in reverse. For example, if a potentiometer
normally gives a full voltage signal to give a maximum speed reference, enabling this
parameter would tell the control to give a minimum speed reference with a full voltage signal
from that potentiometer.
• ENABLE
• DISABLE (default)
18. REVERSE CONTROL
Sometimes used in centrifuge applications, this allows the user to control the drive to go
“down” instead of “up.”
• ENABLE
• DISABLE (default)