DH200F User Manual
©Dyness reserves the copyright of this document.
19
monitoring equipment, fire protection systems, electricity meters, air conditioning, or
access control systems to form an energy storage system. EMS controls the entire system
and enables functions such as on-grid and off-grid control, peak shaving and valley filling,
demand control, smoothing of renewable energy fluctuations, dynamic expansion, and
optimizing energy storage revenue. EMS collects data and signals from local devices and
ensures the safe, reliable, efficient, and economical operation of the energy storage
system through internal control strategies.
Figure 3-8 The appearance of EMS
The EMS parameters and interfaces are as follows
Table 3-7 EMS Interface Parameter Sheet
Program
Specification
clarification
Control
Functions
Dynamic voltage regulation, peak shaving
and load shifting, demand control, dynamic
capacity expansion
User interface
10.1" monitor interface
SD
SD Card Interface
USB-HOST
USB flash drive interface
For software upgrades
RST
Reset port
For local controller reset
Communications
interface
2x Ethernet, 8x RS485, 2x CAN, 1x 4G
Communications
protocol
Ethernet: Modbus TCP, IEC61850 MMS
RS485: Modbus RTU
CAN: Function reservation
DI Input
16 channels, internal self-power supply,
support passive dry contact input signals
Passive dry contact signal
DO Output
16 channels, support normally open/normally
closed
Relay output, relay size:
250Vac/3A or 30Vdc/3A
Indicator light
Power indicator, operation indicator, alarm
indicator, communication indicator, etc.
BMS
BMS module is a high-voltage power circuit management unit specially designed for
energy storage system by our company, which is an intermediate unit connecting battery
clusters and energy storage converter. The BMS module is equipped with circuit breakers,
contactors, fuses, current sensors, battery cluster control management module (HVBCU),
switching power supply, etc. It performs functions such as voltage and current acquisition,
circuit contactor control, and protection for battery clusters.
The BMS stabilizes and secures the battery function by monitoring the battery status in