Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0 75
CChhaapptteerr 66 CCoommmmuunniiccaattiioonn
This section describes the:
DB-9 communication port
X-Slot cards
Remote Monitor Panel and Industrial Relay Card (IRC)
LanSafe Power Management Software
Remote emergency power-off (REPO)
Relay output contacts
Programmable signal inputs
Figure 60 shows the location of the communication options and control terminals on the UPS.
Figure 60. Communication Options and Control Terminals
1
2
1
2
1
2
1
2
1
2
3
DB-9 Communication Port
REPO (normally closed)
REPO (normally open)
Signal Input 2
Signal Input 1
X-Slot Communication Bay #2
X-Slot Communication Bay #1
Relay Output Contacts
66..11 IInnssttaalllliinngg CCoommmmuunniiccaattiioonn OOppttiioonnss aanndd CCoonnttrrooll TTeerrmmiinnaallss
To access and install the communication options and control terminals:
1. Remove the front covers of all cabinets, starting with the top cabinet.
Press and release the handle latch at the bottom of each cover and then lift the cover up and off the
cabinet (see Figure 61).