82 Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0
Table 8. RMP Wire Terminations
From RMP Terminal To IRC Terminal Remarks
J1-1 J1-1
Use Beldon 8690 060 or equivalent
cable
J1-3 J1-3
J1-4 J1-4
J1-5 J1-5
J1-6 J1-6
5. Install the IRC into an open X-Slot communication bay (see Figure 62).
6. To check the operation of the RMP, ensure that the UPS is supplying the load via the inverter or bypass. If
the indicators on the RMP show the appropriate status, then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on the IRC, and the plug–in terminal blocks
for proper seating. If all connections are secure but the RMP still does not operate correctly, replace the
fuse. If this does not correct the problem, contact your service representative for verification that the RMP
is working correctly.
Figure 69. RMP Top Internal View
Plug-in Terminal Block J1
to Industrial Relay Card
NOTE Conduit and wiring
supplied by the customer. The
maximum distance between
the RMP and the UPS is not to
exceed 152.4m (500 ft).
66..22..44 IInndduussttrriiaall RReellaayy CCaarrdd
The IRC uses normally-open or normally-closed dry relay contacts to indicate the UPS status as listed in
Table 9. Figure 70 shows an IRC.
Communication