92 Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0
If the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
87
Normal Mode Startup
To start up the UPS when the load is de-energized:
1. If an optional wall-mounted bypass c abinet is installed, proceed to
Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transfered to UPS mode (see
“Using the Wall-Mounted Bypass Cabinet” on page 97.
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switc h is in the UPS
position(seeFigure59onpage95).
5. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
6. Switch on utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
indicator flashes.
8. Remove the breaker tie from all battery circuit breakers.
9. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
10. Press a ny button on the front panel display to activate the menu
options.
11. Press the
button on the front panel display a nd then press the
button to select the TURN UPS ON/OFF menu.
12. Select the TURN UPS ON option. Press and hold the
button for
three seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.
indicator is flashing, check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
77..22..22 SSttaarrttiinngg tthhee UUPPSS oonn BBaatttteerryy
NOTE Before using this feature, the UPS must have been powered by utility power at least
once.
To start the UPS on battery when the load is de-energized:
1. If an optional wall-mounted bypass cabinet is installed, proceed to Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transferred to UPS mode (see paragraph
7.5 Operating the Wall-Mounted Bypass Cabinet).
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switch is in the UPS position (see Figure 73).
5. Switch all battery circuit breakers to the ON position.
NOTE Leave the battery circuit breaker(s) in the ON position during this operation. If you need
to cancel this operation, wait until the front panel LCD illuminates before switching the
battery circuit breaker(s) off.
6. Wait for the front panel LCD to illuminate.
7. Press any button on the front panel display to activate the menu options.
8. Within three minutes, press the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
82
The following table shows the indicator status and description.
Indicator Status Description
Green
On The UPS is operating normally.
Flashing S The UPS is starting up or is shut down and waiting for power to return.
S A new information message is active.
S Bypass is not available.
Off The UPS is turned off and will not turn on automatically.
Yellow
On The UPS is in Battery mode.
Yellow
On The UPS is in Bypass mode.
Red
On The UPS has an active alarm.
Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 105 for
additional information.
Changing the Language
Press and hold the first button on the left for a pproximately five s econds
to selec t the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable s tartup screen. The default is the Eaton logo and can be
changed to the Mimic sc reen in the User Settings menu.
The bac klit LCD automatically dims after a long period of inac tivity. Press
any button to restore the screen.
Use the two middle buttons (
and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button on the front panel display and then press the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
82
The following table shows the indicator status and description.
Indicator Status Description
Green
On The UPS is operating normally.
Flashing S The UPS is starting up or is shut down and waiting for power to return.
S A new information message is active.
S Bypass is not available.
Off The UPS is turned off and will not turn on automatically.
Yellow
On The UPS is in Battery mode.
Yellow
On The UPS is in Bypass mode.
Red
On The UPS has an active alarm.
Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 105 for
additional information.
Changing the Language
Press and hold the first button on the left for a pproximately five s econds
to selec t the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable s tartup screen. The default is the Eaton logo and can be
changed to the Mimic sc reen in the User Settings menu.
The bac klit LCD automatically dims after a long period of inac tivity. Press
any button to restore the screen.
Use the two middle buttons (
and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button to select
the TURN UPS ON/OFF menu.
9. Select the TURN UPS ON option. Press and hold the
CORD KIT INSTRUCTIONS
Eaton BladeUPS Cord Kit Instructions S 164201721 Rev 2 Draft 13-APR-2010
5
Removing the Existing Power Cords
To remove the existing power cords:
1. If the UPS and internal batteries are already installed, continue to
Step 2. If the UPS and internal batteries are not installed, continue
to Step 15.
2. You MUST shut down the UPS before replacing the cord assembly.
Continue to Step 3 to shut down a standalone UPS.
For parallel shutdown procedures, refer to the Eaton BladeUPS
(12 kVA) User's Guide and then continue to Step 11.
3. Switch the load connector circuit breaker to the OFF (O) position
(see Figure 2).
NOTE The load connector breaker controls the load connector only, not the output power.
4. Press any button on the front panel display to activate the menu
options. Select TURN UPS ON/OFF, TURN UPS OFF, and press the
button.
5. Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and
the
indicator turns off.
6. Switch the UPS battery circuit breaker to the OFF (O) position.
7. If optional EBMs are installed, switch all EBM battery circuit
breakers to the OFF (O) position.
Disconnect the EBM cable from the UPS extended battery
connector.
8. Switch the UPS input circuit breaker to the OFF (O) position.
9. Switch off utility power where the UPS is connected.
10. Unplug the power cords.
button for three seconds, until the UPS stops
beeping.
The UPS starts in Battery mode within two minutes and supplies battery power to your equipment.
77..22..33 IInntteerrnnaall BByyppaassss SSttaarrttuupp
To start the UPS when load is powered by internal bypass:
1. If an optional wall-mounted bypass cabinet is installed, proceed to Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transferred to UPS mode (see paragraph
7.5 Operating the Wall-Mounted Bypass Cabinet).
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switch is in the UPS position (see Figure 73).
5. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position (see
Figure 24).
6. Switch ON the utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
87
Normal Mode Startup
To start up the UPS when the load is de-energized:
1. If an optional wall-mounted bypass c abinet is installed, proceed to
Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transfered to UPS mode (see
“Using the Wall-Mounted Bypass Cabinet” on page 97.
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switc h is in the UPS
position(seeFigure59onpage95).
5. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
6. Switch on utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
indicator flashes.
8. Remove the breaker tie from all battery circuit breakers.
9. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
10. Press a ny button on the front panel display to activate the menu
options.
11. Press the
button on the front panel display a nd then press the
button to select the TURN UPS ON/OFF menu.
12. Select the TURN UPS ON option. Press and hold the
button for
three seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.
indicator flashes.
The UPS starts and transfers to Bypass mode. This may take up to 1 minute.
The
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
87
Normal Mode Startup
To start up the UPS when the load is de-energized:
1. If an optional wall-mounted bypass c abinet is installed, proceed to
Step 2; otherwise, proceed to Step 4.
2. Verify the wall mounted bypass is transfered to UPS mode (see
“Using the Wall-Mounted Bypass Cabinet” on page 97.
3. Proceed to Step 4.
4. Verify that the internal maintenance bypass switc h is in the UPS
position(seeFigure59onpage95).
5. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
6. Switch on utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
indicator flashes.
8. Remove the breaker tie from all battery circuit breakers.
9. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
10. Press a ny button on the front panel display to activate the menu
options.
11. Press the
button on the front panel display a nd then press the
button to select the TURN UPS ON/OFF menu.
12. Select the TURN UPS ON option. Press and hold the
button for
three seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.
indicator flashes while transferring to bypass then goes out with the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D
89
Internal Bypass Startup
To start the UPS when load is powered by internal bypass:
1. If an optional wall-mounted bypass c abinet is installed, proceed to
Step 2; otherwise, proceed to Step 4.
2. Verify the wa ll mounted bypa ss is transfered to Bypass mode (see
“Using the Wall-Mounted Bypass Cabinet” on page 97.
3. Proceed to Step 4.
4. Verify that the maintenance bypass switch is in the SERVICE
position(seeFigure59onpage95).
5. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
6. Switch on utility power where the UPS is connected.
7. Wait for the front panel LCD to illuminate.
The
indicator flashes.
The UPS starts and transfers to Bypass mode. This may take up to
1 minute.
The
indicator flas hes while transfering to bypass then goes out
with the
illuminating to indicate the UPS is operating in Bypass
mode. The load is now powered by utility power.
The display indicates On Manual/Maintenance Bypass.
8. To switch to Normal mode from internal Bypass mode, transfer the
wall mounted by pass to By pass mode (see “Using the
Wall-Mounted Bypass Cabinet” on page 97 and rotate the internal
maintenance bypass switch to the UPS position.
The
indicator illuminates to indicate the UPS is operating in UPS
mode. The load is now powered by UPS.
illuminating to indicate
the UPS is operating in Bypass mode. The load is now powered by utility power.
UPS Operating Instructions