IL17569
Page 12-2
Effective June, 2001
12.1.3 Self Test Failure indication
When a diagnostic self test indicates a failure, an error message is displayed instead of the default metering display, and the Healthy Relay
(K7) is de-energized, no longer indicating proper operation. All other display screens operate normally to permit display of diagnostic information
during troubleshooting. The screen saver is disabled when a warning or failure message is displayed. If more than one warning or failure
condition exists, the FP-5000 scrolls through the multiple error messages. Table 12.1, under the “Display” column, shows all possible displays.
A group of status flags are given in the Status/Control mode that describes the current results of diagnostic self tests. To view these status
flags press the Status/Control button, select “Status” and press enter, select “Self Test Status” and press enter, use the arrow keys to scroll
through the list. Table 12.1, under the “Status Flag” column, lists all of the self test status flags.
Table 12.1 Self Test Displays and Status Flag
Display Status Flag Protection Description Recommended Action
Boot Code Boot Code Disabled The boot code The circuit is not protected, replace
CheckSum Error firmware has FP-5000 immediately
been corrupted Possible Flash reload
Application Code Firmware Disabled The application code The circuit is not protected, replace
Checksum Error firmware has been FP-5000 immediately
corrupted Possible Flash FW reload
RAM Failure at External Disabled A portion of external The circuit is not protected, replace
0X——- RAM RAM cannot be FP-5000 immediately
read or written
RAM Failure at Internal Disabled A portion of the The circuit is not protected, replace
0X——- RAM RAM internal to FP-5000 immediately
the microprocessor
cannot be read
or written
Protection Analog Disabled The analog input The circuit is not protected, replace
Disabled Analog Input has failed to respond FP-5000 immediately
Input Failure or has read a
reference input
incorrectly
Protection Settings Disabled If Fail, the setpoints The circuit is not protected, replace
Disabled Setting have been corrupted FP-5000 immediately
Failure
Display Warning Display Enabled The display content Replace FP-5000 at the earliest
could not be verified convenience
Protection Calibrated Disabled At power up, the The circuit is not protected, replace
Disabled Relay calibration constants FP-5000 immediately
Not Calibrated are corrupted
Nonvolatile RAM Enabled The NVRAM battery If needed, store all log and history
Memory Battery Battery is failing data before power down. This
Warning can be done with the PowerNet
application software. Contact
factory for replacement
instructions.
Real-Time Clock Clock Enabled The real time clock Check the clock for proper time
Warning has malfunctioned and future time keeping. If in error,
replace at the earliest convenience.
EEPROM EEPROM Enabled The EEPROM can- Replace the FP-5000 at the earliest
Warning not be read or convenience. It is possible that the
written FP-5000 will fail to protect the
circuit the next time powered up.