Page 4-11
IL17569
Effective June, 2001
50P-2 PH IOC 2
Pickup (pu): 3.00
Delay (c): 15
Direction: Both
Protection
Setting Group 1
Setting Group 2
Setting Group 3
Setting Group 4
“Protection” Display:
Setting Group 1
Phase Overcurrent
IX Measured OC
IR Residual OC
Unbalance Settings
Main V Protection
Aux V Protection
Freq. Protection
Breaker Failure
Power Factor
Zone Interlocking
Alarms
“Setting Group 1” Display:
* Note: The number of setting groups that are displayed is program-
mable as shown above in the Configuration Settings as “# Set
Grps.” The default # of setting groups is 1, so this “display” will
normally only show “Setting Group 1.” If “# Set Grps” is set to “4,”
then all four setting groups will be displayed as shown below. All
four setting group’s sub-menus display the same settings, therefore
only one setting group is shown here.
Phase Overcurrent
51P PH TOC Curve
51P PH TOC Setting
50P-1 PH IOC 1
50P-2 PH IOC 2
“Phase Overcurrent” Display:
51P PH TOC Curve
Shape: MOD
Reset:Calc
Direction: Both
“51P PH TOC Curve” Display:
51P PH TOC Setting
Pickup (pu): 1.00
Time Mult: 1.00
“51P PH TOC Setting” Display:
50P-1 PH IOC 1
Pickup (pu): 2.00
Delay (c): 0
Direction: Both
“50P-1 PH IOC 1” Display:
“50P-2 PH IOC 2” Display:
Protection
Display 4.12 View Settings