IL17569
Page 5-46
Effective June, 2001
Table 5.12 Protection
Phase Overcurrent PH Settings Default Setting
51P PH TOC Shape: MOD
Reset: Calc
Direction: Both
Pickup: 1.00
Time Mult: 1.00
50P-1 PH OC 1 Pickup: 2.00
Delay (c): 0
Direction: Both
50P-1 PH OC 2 Pickup: 3.00
Delay (c): 15
Direction: Both
IX Overcurrent IX Settings Default Setting
51X PX TOC Shape: XTRM
Reset: Calc
Direction: Both
Pickup: 0.50
Time Mult: 1.00
50X-1 IX OC 1 Pickup: 1.00
Delay (c): 60
Direction: Both
50X-1 IX OC 2 Pickup: 2.00
Delay (c): 600
Direction: Both
IR Overcurrent IR Settings Default Setting
51R IR TOC Shape: XTRM
Reset: Inst
Direction: Both
Pickup: 0.1
Time Mult: 1.00
50R-1 IR OC 1 Pickup: 1.00
Delay (c): 60
Direction: Both
50R-1 IR OC 2 Pickup: 2.00
Delay (c): 600
Direction: Both
46-2 I Unbal Alarm 46-2 I Unbal Alarm Settings Default Setting
Threshold: 0.1
% (I2/I1): 40
Delay (c): 60
47-2 V Unbal Alarm 47-2 V Unbal Alarm Settings Default Setting
Threshold: 50
% (V2/V1): 40
Delay (c): 60