Page 5-45
IL17569
Effective June, 2001
5.6 Default Settings
The Default Settings Table shows all of the System Configuration settings and the remaining settings that are enabled, or turned on, when
the FP-5000 leaves the factory. If the user reverts back to the default settings at any time when the unit is installed in the field, the FP-5000
will revert back to the settings in this table.
Table 5.11 System Config
System Config System Config Settings Default Setting
Frequency: 60
Phase Seq: ABC
CT Connect: 3-wire
PH CT Ratio: 500:5
IX CT Ratio: 500:5
VT Connect: Wye
Main VTR: 100
Aux VTR: 100
Prim Units: No
I/O Config: Default
Prog Logic: Default
Remote Set: Enable
Prg w/Bkr: Either
Remote Bkr: Disable
# Set Grps: 1
Set Ctrl: Local
Disarm Ctrl: Disable
Energy Unit: kWh
TOC Reset T: 5
Bkr Oper PB: Disable
5.5.10 Change Password
The factory default password is 0000. A password of 0000 will
always be accepted during the first 2 minutes after the FP-5000 is
powered up. This allows the user to enter a new password, in case
the password is forgotten.
To change the password, select Change Password setting in the
“Setting Main” display window. Use the single arrow up/down
pushbuttons to move among the 4-character locations of the
password and use the double arrow pushbuttons to change the
value of the 4-character password. Zero through nine and A to Z
are available for each password character.
If the user presses Enter for the password window without changing
any password character the default password of 0 is accepted. The
user can change the password to any non-zero values. However, if
the user changes the password to any non-zero values, pressing
Enter will not permit entry to the settings or the test functions. The
correct password has to be entered.
The same password is valid for setting mode as well as the
test mode.
The FP-5000 password is not valid for PowerNet. PowerNet has its
own password scheme.