Page 3-1
IL17569
Effective June, 2001
3 SPECIFICATIONS
3.1 Table of Specifications
Note that accuracy specifications for the FP-5000 are for operation within the nominal frequency range of 50 Hz or 60 Hz at ± 5 Hz.
Unless stated otherwise, Operating Power Factor is “0.50 Lagging” to “Unity” to “0.50 Leading.”
Control Power: TB101-102 (101 positive for DC)
AC NominalVoltage 100 – 120V AC
AC Excursion Range 55 – 132V AC
AC Frequency Range 50/60 Hz nom. ± 5%
DC Nominal Voltage 48 – 125V DC
DC Excursion Range 38 – 150V DC
Interruption ride through time 5 Cycle Interruption of AC Supply at 120V AC 60 Hz Nominal
Power Consumption 20 VA max.
Current Transformer Inputs: TB4 A, B, C, X
FP-5000-00 FP-5100-00
Nominal(I
nom
): 5A 1A
Ct Rating: Steady state 2 x I
nom
= 10A 3 X I
nom
= 3A
maximum transient 80 x I
nom
= 400A for 1 sec. 100 X I
nom
= 100A for 1 sec.
Ct Burdens < 0.25 VA @ 5A (Nominal) < 0.05 VA @ 1A (Nominal)
Contact Inputs: TB201-204, 206-209, Source TB205, 210
Number of contact inputs Cin1 – Cin8
Rating 40V DC @ 2 mA/C In draw wetting voltage provided
with internal return only
Voltage Transformer Inputs: TB213-217, VA, VB, VC, VX1, VX2
Nominal 0 – 120V AC Line to common
Operating Range 0 – 144V AC (+20%) Line to common
Internal Burden Loading 1 Meg Input Impedance
Reference TB218, Vg internal 120 ohm PTC to chassis ground
Relay Output:
Number & type of output contacts 2 Form C, NO & NC TB103-105, 106-108
5 Form A, NO only
TB109/110, 111/112, 113/114, 115/116, 117/118