IL17569
Page 3-2
Effective June, 2001
Relay Output Contacts Rating: Both Form A & C
Momentary Make 30A AC/DC for 0.25 s.
Break 0.5A @ 125V DC (resistive)
Break 5A @ 120V AC
Continuous 5A @ 120/240V AC
5A @ 30V DC
IPONI Communications: TB3 J1
Baud Rate 9600 Fixed
Max. distance 10,000 feet
Protocol INCOM Slave
Media Shielded Twisted pair - CH IMPCABLE; BELDEN 9463, 3072F
Signal lines J1-1, J1-2 polarity not needed
Shield J1-3 Filter referenced to chassis
DC input impedance ~2 ohms
AC input impedance @ 100 kHz > 30k/100 ohms unterminated/terminated - Switch
Accessory Bus: TB3 J2, - FUTURE INTERFACE
Baud Rate 9600 Fixed
Max. distance 10,000 feet
Protocol INCOM
Media Shielded Twisted pair - CH IMPCABLE: Belden 9463, 3072F
Signal lines J2-1, 2-2 polarity not needed
Shield J2-3 Filter referenced to chassis
DC input impedance ~2 ohms
AC Input impedance @ 100 kHz > 100 ohms (permanent termination resistor)
Zone Interlock: TB3 J3
Zone Out J3-1 Open collector output ~ 4.5V to common
Zone In J3-4, Approximately 300K ohms input impedance
Zone Common J3-2, 3-5 internally connected
Zone Shield J3-3 referenced direct to chassis – NOT REQUIRED
Cable 14-18 AWG Twisted Pair <250' between 1
st
and last unit
RS-232: Front temporary programming monitor port
PowerPort Connection
Baud Rate 38.4 kB, 19.2 kB, 9.6 kB
Connector Standard 9-Pin D Subminiature, DCE Connection P2, 3, 5
Protocol INCOM ASCII Slave
Cable Shielded & restricted to < 3 meters in length

Table of Contents