Page 5-3
IL17569
Effective June, 2001
5.3 FP-5000 Setting Table
NOTE: All voltage settings are in secondary units. All current settings are in per unit. All System settings are in primary units. Time delay
setting is in cycles (c), seconds (s), or minutes (m).
Program Date: Control Schematic:
FP-5000 Relay ID: Breaker ID:
Work Order #: Line Protected:
Table 5.1 System Config
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Frequency: Nominal system 50 Hz or 60 Hz 60 5.5.1
operating frequency
Phase Seq: Nominal system phase ABC or ACB ABC 5.5.1
sequence or rotation
Ct Connect: Ct connect determines how 3-wire, 4Ct In, 4Ct Ig 3-wire 5.5.1
residual current IR is calculated 8.2
3-wire: 4th Ct is independent
4Ct In: 4-wire system with
4th Ct on neutral conductor
4Ct Ig: 4-wire system with
4th Ct on ground conductor
PH Ct Ratio: Ct ratio of the phase Inom to 6000 500:Inom3 5.5.1
current Cts (Increments of Inom)
IX Ct Ratio: Ct ratio of the fourth Ct Inom to 6000 500:Inom3 5.5.1
(Increments of Inom)
VT Connect: Voltage transformer Wye or Delta Wye 5.5.1
connection 6.3.2
Main VTR: Main voltage 1 to 8000 100 5.5.1
transformer ratio:1 (Increments of 1)
Aux VTR: Auxiliary voltage 1 to 8000 100 5.5.1
transformer ratio:1 (Increments of 1)
Prim Units: Selection of primary or Yes, No No 5.5.1
secondary units of displayed
values
I/O Config: Default input/output Default or Custom
1 Default 5.5.1
configuration or customized
input/output
Prog Logic: Default or custom Default or Custom
1 Default 5.5.1
Programmable logic settings
Remote Set: Enables or disables remote Enable or disable Enable 5.5.1
download setpoints capability
from rear communication port