Page 4-9
IL17569
Effective June, 2001
Min <Variable>
(Variable) Magnitude
Date mm/dd/yy
Time hh:mm:ss
Where <Variable> (Variable) =
<IA Current> (IA)
<IB Current> (IB)
<IC Current> (IC)
<IX Current> (IX)
<IR Current> (IR)
<VAB Voltage> (VAB)
<VBC Voltage> (VBC)
<VCA Voltage> (VCA)
<VA Voltage> (VA)
<VB Voltage> (VB)
<VC Voltage> (VC)
<System Watts> (M Watts)
<System Vars> (M VAR)
<System VA> (MVA)
<Frequency> (Freq)
<Apparent PF> (Apt PF)
<Displacement PF> (Disp PF)
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurance.
The minimum values for each of the above parameters is compared
to the last minimum value for that parameter every 32 cycles. If the
new value is less than the last minimum, the value is updated.
Power Factor Minimum is the most leading power factor value
measured.
Table 4.2 Minimum Sub-menu
4.6.1.5 Selecting the “Minimum” Sub-menu
This menu allows the user to view the following system parameters.
(See Display 4.8 Minimum Sub-menu.)
Minimum currents (IA, IB, IC, IX, IR)
Minimum L-L Voltages (VAB, VBC, VCA)
Minimum L-N Voltages (VA, VB, VC)
Minimum Power (Watt, Var, VA)
Minimum Frequency
Minimum Power Factor (Apparent, Displacement)
Display 4.8 Minimum Sub-menu
Min Rst Date & Time
Date mm/dd/yy
Time hh:mm:ss
4.6.1.6 Selecting the “Maximum” Sub-menu
This menu allows the user to view the following system
parameters. (See Display 4.9 Maximum Sub-menu.)
Maximum currents (IA, IB, IC, IX, IR)
Maximum L-L Voltages (VAB, VBC, VCA)
Maximum L-N Voltages (VA, VB, VC)
Maximum Power (Watt, Var, VA)
Maximum Frequency
Maximum Power Factor (Apparent, Displacement)
Max <Variable>
(Variable) Magnitude
Date mm/dd/yy
Time hh:mm:ss
Min Rst Date & Time
Date mm/dd/yy
Time hh:mm:ss
Table 4.3 Maximum Sub-menu
Where <Variable> (Variable) =
<IA Current> (IA)
<IB Current> (IB)
<IC Current> (IC)
<IX Current> (IX)
<IR Current> (IR)
<VAB Voltage> (VAB)
<VBC Voltage> (VBC)
<VCA Voltage> (VCA)
<VA Voltage> (VA)
<VB Voltage> (VB)
<VC Voltage> (VC)
<System Watts> (M Watts)
<System Vars> (M VAR)
<System VA> (M VA)
<Frequency> (Freq)
<Apparent PF> (Apt PF)
<Displacement PF> (DisP PF)
Display 4.9 Maximum Sub-menu
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurance.
The maximum values for each of the above parameters is com-
pared to the last maximum value for that parameter every 32 cycles.
If the new value is greater than the last maximum, the value is
updated. Power Factor Maximum is the most lagging power factor
value measured.