Page 4-3
IL17569
Effective June, 2001
4.3 Pushbuttons
The front operations panel supports 15 membrane switch
pushbuttons. Pressing any of the pushbuttons will initiate many
of the FP-5000 functions and actions. This section gives a complete
description of each pushbutton and its functions. The pushbuttons
can be grouped logically into the 6 display modes, reset and
breaker control.
1. Reset 5. Status/Control
2. Monitor 6. Set (Settings)
3. View Setting 7. Test
4. Log 8. Close Open Breaker
The center section consists of display navigation buttons:
1. Previous
2. Up/Down (single arrow)
3. Up/Down (double arrow)
4. Enter
“Reset” Pushbutton:
The “Reset”pushbutton performs many “Reset”
functions, one of which resets the display to
show the default rms current and voltage display
screen from any display menu, when the relay
is in normal monitoring mode.
The FP-5000 has a “Reset” menu, which is
accessed by pressing the “Reset” pushbutton
when the unit is in normal monitoring mode. This
menu allows the user to reset all of the relay
functions: trips, alarms, peak current and power
demands, min/max values, history log param-
eters, relays, and the data logger. There is no
password protection for the reset functions.
(See Display 4.2)
Reset Main
Trip
Alarm
Bkr Lockout
Slow Bkr ALM
Relay
Peak Demand Values
Min/Max Values
History Log
Datalog
Energy
Display
Diag Warnings
By selecting a Reset sub-menu function listed above by using the
Up/Down arrow and “Enter” pushbutton, the user can reset that
function simply by pushing the “Enter” pushbutton again. The example
below shows the “Trip Flag” sub-menu reset display screen.
Reset Trip
Press
ENTER To Confirm
PREVIOUS To Cancel
Display 4.2 Reset
Table 4.1 Transient Display Messages
“Display Message” Display Mode Cause
Functions Programmed to Flashing a few seconds in When entering PLC, Cin and Cout
default. They can be the setting-edit mode in the setting-edit mode if they
viewed only. are disabled
See System Config.
Fault Test is Off! 5 seconds in Test mode When stopping fault simulation if
the test was complete
Zone Interlock Output is On 5 seconds in Test mode When turning the Zone Interlock
output on if it is on
Zone Interlock Output Is Off 5 seconds in Test mode When turning the Zone Interlock
output off if it is off