Page 5-31
IL17569
Effective June, 2001
5.4 Logic Input Settings
Table 5.10 Logic Input Setting Options
Logic Input (IN1, IN2, IN3, & IN4) Programming Option Settings: Logic input settings for the 8 logic categories
Input Category “Available Setting Options” Setpoint Range/
Value Selection
Unused Unused Direct or Negated
Pickup PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2, Direct or Negated
50X-3, 50R-1, 50R-2, 50R-3, 50P-1, 50P-2, 50P-3, 51P, 51X, 51R, 59A-1,
59A-2, 27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1,
47-2, 81U-1, 81U-2, 81O-1, 81O-2, BF, 55A PF,
Trip PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2, Direct or Negated
50X-3, 50R-1, 50R-2, 50R-3, 50P-1, 50P-2, 50P-3, 51P, 51X, 51R, 59A-1,
59A-2, 27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1,
47-2, 81U-1, 81U-2, 81O-1, 81O-2, BF, 55A PF,
Logic LG1, LG2, LG3, L54, LG5, LG6, TG1, TG2, TG3, TG4, Direct or Negated
TG5, TG6, Q1, or Q2
Inputs Cin1, Cin2, Cin3, Cin4, Cin5, Cin6, Cin7, Cin8, or ZI In Direct or Negated
SysAlm Watt, VAR, VA, WattDmd, VARDmd, VADmd, CurDmd, V THD, I THD, Direct or Negated
BkrOps, Sum I, or AllAlm
Breaker OpenBkr, CloseBkr, Open, Closed, BkrFail, SlowBkr, StateAlm, Direct or Negated
Mntr1Alm, Mntr2Alm or All Alm
Comm Comm1, Comm2, Comm3 or Comm4 Direct or Negated

Table of Contents

Related product manuals