IL17569
Page 5-4
Effective June, 2001
Table 5.1 System Config (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Prg w/Bkr: Program relay with breaker Open or Either Either 5.5.1
open or closed (requires 52a
or 52b input)
Remote Bkr: Enable or disable remote Enable or disable Disable 5.5.1
breaker open/close control
from rear comm port
# Set Grps: Select the max. number 1, 2, 3, or 4
1 1 5.5.1
of different Protection 9.7
Setting Groups
Set Ctrl: Select the means of control for Local, Local+ Local 5.5.1
selecting the active setting group Communications, 9.7
Communications, Cin
Disarm Ctrl: Enable/disable of the Enable or disable 2 Disable 5.5.1
Arm/Disarm control from the front 11.2.5.1
panel “Test Mode” (Output Trip1
& Trip2 ONLY)
Energy Unit: This is the selection for “Energy kWh or MWh kWh 5.5.1
Units” killo- or Mega- Watt-hours 4.6.1.3
TOC Reset T: Time Overcurrent RESET Time 1 to 20 cycles 4 5 5.5.1
Delay in cycles. Used when time (Increments of 1) 5.5.2.1
option for reset is chosen 8.3.2
Bkr Oper PB: Front panel Breaker Open/Close Enable or disable Disable 5.5.1
pushbutton function Enable
1 This setting affects other settings. The user must save settings after changing this setting, which will take the user
out of program mode. The user must then re-enter program mode to continue programming the remaining settings.
2 If enabled, the user must go to the “Test Mode” by pressing the “test button”, select Arm/Disarm Trip, then select
Arm Trip or Disarm Trip setting.
3 Ct secondary rating is automatically detected: I
nom = 1A or 5A.
4 This setting is the programmed time delay for the T Delay setting of the time overcurrent Reset setting. See TOC
Curve settings for 51P, 51R, and 51X elements.