IL17569
Page 12-6
Effective June, 2001
Table 12.5 Event Pickup, or Dropout Cause Table — continued
Cause Cause Description Value Given
59A OV Auxiliary Over Voltage has picked Voltage Pickup Status – contains the status flags that
up or dropped out describe all under and over voltage pickups
27A UV Auxiliary Under Voltage has picked Voltage Pickup Status – contains the status flags that
up or dropped out describe all under and over voltage pickups
46 Iunbal Phase Current Unbalance has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
47 Vunbal Phase Voltage Unbalance has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
81 UF Under Frequency has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
81 OF Over Frequency has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
BF Breaker Failure has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
55A PF Apparent Power Factor has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
55D PF Displacement Power Factor has Miscellaneous Pickup Status – contains the status flags
picked up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
Zin Trip Zone Interlock Trip has picked Miscellaneous Pickup Status – contains the status flags
up or dropped out that describe all unbalance, frequency, breaker failure,
power factor, and zone interlocking pickups
PwrAlm The system alarm for Watt, VA, or System Alarm Pickup Status – contains the status flags for
VAR has picked up or dropped out all system alarms
PwrDmdAlm The system alarm for Watt demand, System Alarm Pickup Status – contains the status flags for
VA demand, or VAR demand has picked all system alarm pickups
up or dropped out
CurDmdAlm The system alarm for Current Demand System Alarm Pickup Status – contains the status flags for
has picked up or dropped out all system alarm pickups
THD CurAlm The system alarm for Current Total System Alarm Pickup Status – contains the status flags for
Harmonic Distortion has picked up all system alarm pickups
or dropped out
THD VolAlm The system alarm for Voltage Total System Alarm Pickup Status – contains the status flags for
Harmonic Distortion has picked up all system alarm pickups
or dropped out