IL17569
Page 2-6
Effective June, 2001
Table 2.1 Minimum List of Functions Which MUST be Programmed (continued)
Setting Default Incr Display User
Setting
IX Overcurrent
51X Ix TOC Shape XTRM List IT, I2T, 14T, FLAT, MOD, VERY, XTRM, IECA,
IECB, IECC
51X Ix TOC Reset Calc List Inst, Calc, T Delay
51X Ix TOC Pickup 0.50 0.01 0.10-4.00 p.u., “Disable”
51X Ix TOC Time Multi 1.00 0.01 0.05-10.00 p.u.
50X1 Ix OC Pickup 1.00 0.01 0.10-20.00 p.u., “Disable”
50X2 Ix OC Delay 60 1 0-9999 cycle
50X2 Ix OC Pickup 2.00 0.01 0.10-20.00 p.u., “Disable”
50X2 Ix OC Delay 600 1 0-9999 cycle
IR Residual Overcurrent
51R Ir TOC Shape XTRM List IT, I2T, 14T, FLAT, MOD, VERY, XTRM, IECA,
IECB, IECC
51R Ir TOC Reset Inst List Inst, Calc, T Delay
51R Ir TOC Pickup 0.1 0.01 0.10-4.00 p.u., “Disable”
51R Ir TOC Time Multi 1.00 0.01 0.05-10.00 p.u.
50R1 Ir OC Pickup 1.00 0.01 0.10-20.00 p.u., “Disable”
50R1 Ir OC Delay 60 1 0-9999 cycle
50R2 Ir OC Pickup 2.00 0.01 0.10-20.00 p.u., “Disable”
50R2 Ir OC Delay 600 1 0-9999 cycle