Page 4-21
IL17569
Effective June, 2001
4.6.3 Logs
There are three types of logs: Trip, Event
and History Log.
• The Trip Log provides details for the most
recent 16 trip events.
• The Event Log is a sequence of events
report for the last 100 events.
• The History Log provides a counter for
number of operations and/or events.
See Section 12 for log details.
Press the “Log” pushbutton to go in to Log
Mode and to view the FP-5000 Trip, Event
and History Logs. The red LED in the upper
left-hand portion of the pushbutton area will
illuminate while you are in the Log Mode.
The chart below shows the options provided
by pressing the “Log” pushbutton.
Display 4.13 Log Main Menu
Log Main
Trip Log
Event Log
History Log
4.6.3.1 Trip Log
The Trip Log stores the trip information for the last 16 trip events.
An example of the “Trip Log Display” showing two trip events is
displayed below. The #1 event will always show the latest trip event.
When the 16 trip event logs are filled, the FP-5000 will overwrite the
oldest log.
Trip Log
1 50P IOC 1/19/01
2 Relay Test 10/25/00
3 0/0/00
By using the “Up/Down” pushbuttons, the user can select any trip
event. Using the example above, the #1 event is an “instantaneous
overcurrent” trip on phase that happened 1/19/01. By selecting this
event with the Up/Down arrows and pushing the “Enter” pushbutton,
the user can view additional information about the event. Display
4.14 is an example of the trip log information.
150P IOC 1/19/01 Display Meanings
Trip #: 2 Trip #
Time: 13:36:06.109 Time of trip
Event #: 27 Event #
Cause: 50P IOC Cause of trip
Fit Type: AG Fault Type
Set Seq Num: 0 Setting Sequence Number
WaveCap Index 34 Waveform Capture Index
ActiveSetGrp: 1 Active Setting Group
TripStatus: Processed Trip Status
TOC Time MS NA Time Overcurrent Trip Time
Input Status Input Status
Output Status Output Status
IOC Pickup Status Inverse Time Overcurrent Status
V Ph Pickup Status Voltage Phase Pickup Status
TOC Pickup Status Time Overcurrent Pickup Status
Misc. Pickup Status Miscellaneous Pickup Status
OC Trip Status Overcurrent Trip Status
Misc. Trip Status Miscellaneous Trip Status
Volt Trip Status Voltage Trip Status
Output Gate Status Output Gate Status
Logic Block Status Logic Block Status
Logic Gate Status Logic Gate Status
SYSALM Pickup System Alarm Pickup
SYSALM TimeOut System Alarm Timeout
Breaker Status Breaker Status
OGx Input Settings Output Gate Input Settings
OGx Input State Output Gate Output Setting
Trip Test Status Trip Test Status
RMS Values RMS Values of Voltages, Currents
V&I Phasors Voltage & Current Phasors
Display 4.14 Trip Log #1 Example Display
4.6.3.2 Event Log
The Event Log provides a time-stamped list of the most recent 100
events. Select “Event Log” in the Log menu to view these events.
The logged events include pickup and dropout of protective or control
functions, trip, change of state for contact input and outputs, and
setting changes. The data logged for each event includes the event
number, event I.D., a time stamp, and an optional 2 byte parameter.
The user may disable logging of any event category except a trip or
a self-test warning. By using the “Up/Down” pushbuttons, the user
can select any event and retrieve its information. Refer to section
12.2.1 for more information on the Event Log.
4.6.3.3 History Log
The History Log provides the Total History Log and the Breaker
History Log of FP-5000 trip events and breaker operations. This
information is useful for breaker maintenance. See Displays 4.15
and 4.16 for History Log displays.