M-Max Series adjustable frequency drive
8 For more information visit: www.eaton.com
MN04020002E
February 2010
Table 3: Technical Data (continued)
Rated motor currents for normal four-pole internally-cooled and surface-cooled three-phase asynchronous motors
(1500 rpm at 50 Hz, 1800 rpm at 60 Hz).
Allocated motor output at a maximum ambient temperature of +40ºC and a maximum pulse frequency of 4 kHz.
Operation with reduced load torque (about –10% MN).
Control signal terminals
The control section, with the corresponding control signal terminals, is shown below.
Figure 3: Schematic Arrangement and Designation of Control Signal Terminals
Part Number
Rated
Opera-
tional
Current
Overload
Current
(150%) Assigned Motor Rating
Installation
Size
I
e
I
e150
P (230V, 50 Hz) P (230V, 60 Hz)
[A] [A] [kW] [A]
[hp] [A]
Power Connection Voltage: 3 AC 400V/460V, 50/60 Hz (323 – 528V ± 0%, 45 – 66 Hz ± 0%)
MMX34AA1D3.... 1.3 2.0 0.37 1.1 1/2 1.1 FS1
MMX34AA1D9.... 1.9 2.9 0.55 1.5 3/4 1.6 FS1
MMX34AA2D4.... 2.4 3.6 0.75 1.9 1 2.1 FS1
MMX34AA3D3.... 3.3 5.0 1.10 2.6 1-1/2 3 FS2
MMX34AA4D3.... 4.3 6.5 1.50 3.6 2 3.4 FS2
MMX34AA5D6.... 5.6 8.4 2.20 5.0 3 4.8 FS2
MMX34AA7D6.... 7.6 11.4 3.00 6.6 4 7.6 FS3
MMX34AA9D0.... 9.0 13.5 4.00 8.5 5.5 7.6 FS3
MMX34AA012.... 12.0 18.0 5.50 11.3 7-1/2 11 FS3
MMX34AA014.... 14.0 21.0 7.50
(15.2)
10
14 FS3
12367
8
9
10 25 24
4 5 13 14 15 16 18 20 22 23 26
AI2
DO– GND
DI4 DI5 DI6 AO DO+
R13
R14 – R24
+
10V AI1 GND
24V
DI-C
DI1 DI2 DI3 A B R22 R21