Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 205
The software’s mass configuration capabilities make installation and maintenance easy, which minimizes the
effort required and benefits the bottom line. Eaton’s cost-effective Intelligent Power Software manages up to
ten devices at no charge, with licences for up to 100 devices or even an unlimited number also available.
Contact your Eaton Sales representative for additional information.
88..44 BBuuiillddiinngg AAllaarrmm MMoonniittoorriinngg
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or over-
temperature alarms. The customer interface terminals for external connections are located inside the UPS. You
should use twisted-pair wires for each alarm input and common.
88..55 GGeenneerraall PPuurrppoossee RReellaayy CCoonnttaacctt
One general purpose relay contact is provided as a standard feature on the UPS. The alarm contact is located
inside the UPS on the customer interface terminal board. You can use a normally-closed or normally-open
contact. If the state of the contact changes from the state you specify as normal, a signal is issued.
You can connect this contact to equipment at your facility (such as a light or an alarm bell) to let you know when
an alarm is active on the UPS. This feature is useful if the UPS is located in a remote area where the UPS horn
may not be heard immediately.
Contacts should not be operated in excess of 30 Vac @ 5A maximum.
88..66 RReemmoottee MMoonniittoorr PPaanneell IIII
As an option, an RMP II can be installed to monitor the operation of the UPS system from virtually any location
within the facility, up to 150m (500 ft) from the UPS. The RMP II contains backlit status indicators and a local
horn. The RMP II can be flush–mounted or surface–mounted on a desktop, or secured to a wall. Figure 127
shows an RMP II.
Figure 127. Remote Monitor Panel II