Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 207
Figure 128. Relay Interface Module II
The RIM II can provide the status and alarm signals shown in Table 38.
Table 38. Customer Interface Connectors
Status J1 through J4 Description
UPS AVAILABLE Pins 1 and 12 Contacts are closed when the UPS is operating in Online mode or ready to supply the
load.
UPS OFFLINE Pins 3 and 13 Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Online mode.
BATTERY WEAK Pins 5 and 14 Contacts are closed when approximately two minutes of battery time is remaining
before the critical load is lost.
UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected.
88..88 SSuuppeerrvviissoorryy CCoonnttaacctt MMoodduullee IIII
An optional SCM II establishes an interface between the UPS system and the customer's monitor. This
interface allows the customer to monitor operational status of the UPS system equipment. The SCM II can be
flush–mounted or surface–mounted on a desktop, or secured to a wall. Figure 129 shows the SCM II.