82 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
1. If not already installed, install the LAN and telephone drops.
2. Unfasten the front door latch and swing the door open (see Figure 16).
3. Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes (see Figure 31).
4. Reinstall the interface entry plates and install the conduit.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards. See Figure 37 and
Figure 43 for X-Slot communication bay locations.
6. Close the front door and secure the latch.
7. Refer to the manual supplied with the X-Slot card for operator instructions.
Figure 43. X-Slot Communication Bays
X-Slot Communication Bay 1
X-Slot Communication Bay 2
X-Slot Communication Bay 3
X-Slot Communication Bay 4
44..1100 IInnssttaalllliinngg aa RREEPPOO SSwwiittcchh
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. Figure 44
shows a REPO switch.
NOTE Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs 4.2 Unloading the UPS Cabinet from the Pallet through
4.9 Installing Interface Connections.
NOTE When installing the REPO switch, you must install conduit between the device and the
UPS cabinet for wiring the switch.