EasyManua.ls Logo

Eaton Power Xpert 9395P - Page 91

Eaton Power Xpert 9395P
239 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Figure 34. ISBM Section Power Terminal Detail AA
Phase A (E6)
Phase C (E8)
Phase B (E7)
AC Input to
UPS Rectifier
Phase A (E1)
Phase C (E3)
Phase B (E2)
AC Input to
UPS Bypass
`
Front
Section A–A
Ground Terminals
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration.
44..88..22 BBaatttteerryy PPoowweerr WWiirriinngg
When sizing the battery system, do not exceed the internal battery charger capabilities. See
Chapter 10 Product Specifications for maximum battery charger currents.
To install wiring to connections:
NOTE An installed FI-UPM is always designated as UPM 4.
UPS System Installation

Table of Contents

Other manuals for Eaton Power Xpert 9395P

Related product manuals