58
Appendix A—Technical data and specifi cations
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Attribute Description Specification
Safety/protections Overvoltage protection Yes
Overvoltage trip limit 230 V drives: 456 V
480 V drives: 911 V
600 V drives: 1100 V
Undervoltage protection Yes
Undervoltage trip limit 230 V drives: 211 V
480 V drives: 370 V
600 V drives: 550 V
Earth fault protection Yes, Default: 15% Motor FLA
Min: 0% Motor FLA
Max: 30% Motor FLA
Input phase supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protection Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection Yes
DC bus overvoltage control Yes
Short-circuit protection of 24 V
referencevoltages
Yes
Surge protection Yes (differential mode 2 kV; common mode 4 kV
 230 V drives: 275 Vac, 10,000 A
 480 V drives: 320 Vac, 8000 A
 600 V drives: 385 Vac, 10,000 A
Common coated boards Yes (prevents corrosion)
RTC Battery 3.6V Lithium Battery (Able ER14250)
ROHS compliant
Follow local Recycling program to dispose.
10,000 hour life
*Only active when Power Removed
Efficiency Drive efficiency ratings 230 V: FR0 = DG1-323D7EB-C20C: 96.37%
FR0 = DG1-324D8EB-C20C: 96.38%
FR0 = DG1-326D6EB-C20C: 96.31%
F
R1 = 96.7%
FR2 = 97.4%
FR3 = 97.2%
FR4 = 97.4%
FR5 = 97.7%
FR6 = 97.5%
480 V: FR0 = DG1-342D2EB-C20C: 97.23%
FR0 = DG1-343D3EB-C20C: 97.33%
FR0 = DG1-344D3EB-C20C: 97.27%
FR0 = DG1-345D6EB-C20C: 97.15%
FR1 = 97.7%
FR2 = 97.9%
FR3 = 97.7%
FR4 = 98.0%
FR5 = 98.2%
FR6 = 97.9%
600 V: FR1 = 98.1%
FR2 = 98.2%
FR3 = 97.7%
FR4 = 98.3%
FR5 = 98.6%
FR6 = 98.5%
Table 36. PowerXL Series, continued