Appendix C—Ratings, Cooling and Power Losses—Inline
42 S801+ Soft Starter MN03900002E—November 2012 www.eaton.com
Severe Duty—30 Second Ramp and/or 450% Current Limit at 50°C—Inline Connection
Notes
1.0SF = 1.0 Service Factor.
1.15SF = 1.15 Service Factor.
Maximum
Current
Three-Phase Motors
Catalog
Number
kW Rating (50 Hz) hp Rating (60 Hz)
230V 380–400V 440V 200V 230V 460V 575–690V
1.0SF 1.0SF 1.0SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Frame Size N
22 5.510 115 5 7.55 15102015S801+N37…
42 1118.5221010151030254030S801+N66…
Frame Size R
65 15 30 33 15 15 20 15 50 40 50 50 S801+R10…
80 22 40 45 25 20 30 25 60 50 75 60 S801+R13…
Frame Size T
115 33 59 63 30 30 40 30 75 75 100 100 S801+T18…
150 45 80 90 50 40 50 50 100 100 150 125 S801+T24…
192 55 100 110 60 50 75 60 150 125 200 150 S801+T30…
Frame Size U
240 75 110 147 75 60 75 75 200 150 200 200 S801+U36…
305 90 160 185 100 75 100 100 250 200 300 250 S801+U42…
Frame Size V
240 75 110 147 75 60 75 75 200 150 200 200 S801+V36…
305 90 160 185 100 75 100 100 250 200 300 250 S801+V42…
365 110 185 220 125 100 150 125 300 250 350 300 S801+V50…
420 129 220 257 150 125 150 150 350 300 450 350 S801+V65…
480 147 257 295 150 150 200 150 400 350 500 450 S801+V72…
525 160 280 335 150 150 200 150 450 350 500 450 S801+V85…
575 172 303 370 200 150 250 200 500 450 600 500 S801+V10…