General Information
S801+ Soft Starter MN03900002E—November 2012 www.eaton.com 47
Thermal Memory
This parameter is not the same as Thermal Overload.
At 100% Thermal memory the soft starter will stop with
a RED status LED.
At 99% thermal Memory a START command will be
allowed BUT, as soon as 100% is again reached, as it will
be during the start sequence, the soft starter will again
stop.
Cycling 24 Vdc control power will not reduce the
Thermal Memory value.
Fault Occurrence Categories
Immediately when START command is issued.
During the START ramp, before the internal bypass
contactors close.
During the Internal Bypass Contactor closure event.
Anytime during the RUN operation.
During the STOP (SOFT STOP) command.
Status LED Indication Conditions
RED
Active fault is present, cannot RESET.
GREEN
Not responding to START command from field wiring.
LEVEL Sense
Insufficient voltage at Terminal “P”.
Insufficient voltage at Terminal “1”.
EDGE Sense
Cycle 24 Vdc at Terminal “1”
Insufficient voltage at Terminal “P”.
Insufficient voltage at Terminal “1”.
OFF—All
Check for loss of 24 Vdc control power and/or less
than 17 Vdc.
Check Terminal Block for condition and security.
Verify 24 Vdc at appropriate terminals
Verify proper operation and capacity of control power
supply.
START Command Troubleshooting
From the Terminal Block
Verify that Terminal “P” is energized continuously.
Verify that 24 Vdc is applied to Terminal “1” to issue
START command.
If Terminals “P” and “1” are tied together, verify that
both Terminals receive 24 Vdc START signal.
If Start Control parameter is set to EDGE, verify that
24 Vdc has been cycled (removed, then reapplied)
after faults have been reset.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton S801+ Series and is the answer not in the manual?

Eaton S801+ Series Specifications

General IconGeneral
Product SeriesS801+
CategoryController
Input Voltage24 VDC
Output Voltage24 VDC
Number of Inputs8
Protection ClassIP20
Communication ProtocolModbus

Related product manuals