Step 2 – Setup first (or only) CBC
1 Connect a null modem cable from the RS232 port of the CBC to the serial
port of the PC.
2 From the DCTools CellSure Battery Monitoring System Summary (Home)
screen, go to Configuration > Communications and check the following
settings:
RCP address: 150 (default)
Baud Rate Port RS485: B 19200 Baud
Protocol Port RS485: Rcp
Step 3 – Setup additional CBCs (if fitted)
As required, repeat the previous step for the second, third and fourth CBCs,
except set the RCP addresses to 151, 152 and 153 respectively.
Step 4 – Configure the SM65 to operate with CellSure
1 From the DCTools System Summary (Home) screen, go Configuration >
External I/O to display the External Input/Output Communications
view.
2 Scroll down to CellSure Battery Controller (CBC) and set Fitted to True.
3 From the DCTools System Summary (Home) screen, go to CBC to display
the CellSure Battery Controller (CBC) Summary view.
4 Set Number of CBCs as appropriate.
5 To allow the SM65 to use the average string temperature from the
CellSure battery temperature sensor (instead of its own battery
temperature input) click D next to Batt Temp Source and select CBC
Average from the list.
Step 5 – Configure the DCTools / PowerManagerII communications settings
Create a new connection for CellSure in DCTools and/or PowerManagerII
with the following settings. Then check that DCTools or PowerManagerII
communicates correctly.
Comms Enabled : True
Protocol : S3P Passthrough
Connect Using : Local Network
S3P Address : 1:150 (Note 1)
Server IP Address : Enter the SM65 IP Address
Server Port : 14000
Telnet : Cleared