3.2. GLOBAL SETTINGS
The GLOBAL submenu contains the following parameters:
• SYS (System Units of Measure)
• LOCATIONS (Number of Measurement Locations)
3.2.1. System Units of Measure [SYS]
The units of measure used by the transmitter.
[Menu path: SETTINGS > GLOBAL > SYS]
Default: I-P (Imperial System of Units)
Optional Settings: SI (International System of Units)
U/M=I-P: The transmitter system of units and abbreviations used in this document are as follows:
• Area: square feet (sq. ft)
• Length: feet (ft)
• Velocity: feet per minute (FPM)
• Volumetric airflow: cubic feet per minute (CFM)
• Pressure: inches of water gauge (iWG)
• Temperature and Dewpoint: degrees Fahrenheit (°F)
• Relative Humidity: percent relative humidity (% RH)
• Enthalpy: British thermal units per pound (Btu/lb)
U/M=SI: The transmitter system of units and abbreviations used in this document are as follows:
• Area: square meters (sq. m)
• Length: meters (m)
• Velocity: meters per second (m/s)
• Volumetric airflow: liters per second (L/s)
• Pressure: Pascals (Pa)
• Temperature and Dewpoint: degrees Celsius/centigrade (°C)
• Relative Humidity: percent relative humidity (% RH)
• Enthalpy: Kilojoules per kilogram (kJ/kg)
Changing the system of units restores factory default settings. Modifications made by the user are
lost.
Configure for 2 locations at initial power-up or prior to modifying any factory default settings.
3.2.2. Measurement Locations [LOCATIONS]
The number of measurement locations the transmitter serves.
The measurement location parameter is only visible with EB-Flow2 remote transmitters. Advantage
IV dual location transmitters are model specific.
[Menu path: SETTINGS > GLOBAL >↓ LOCATIONS]
Default: 1
Optional Settings: 2