Relative humidity, enthalpy and dew point measurement accuracy is percent of reading. Decreasing
the full scale does not improve measurement accuracy. Today’s application controllers generally
have sufficient accuracy and input resolution to use the default output scaling of the transmitter
3.6. RS-485 NETWORK SETTINGS
One RS-485 network connection is provided with the following transmitter models:
• Advantage IV Product Line
o Models with the third digit of the model code equal to B, C, or N
• EB-Flow2 Product Line
o Models with the first digit after EF- equal to N
The RS-485 submenu contains the following parameters:
• NETOUT (RS-485 Network Protocol)
• NETADDR (Network Address)
• NETBAUD (Baud Rate)
• PARITY (Parity)
• NETDI (Device Instance Number)
• RS485 COM (Enable RS-485 Communications)
3.6.1. RS-485 Network Protocol [NETOUT]
The network protocol of the RS-485 connection.
[Menu path: SETTINGS >↓ RS485 > NETOUT]
Default: BACNET (BACnet MS/TP)
Optional Settings: MODBUS (Modbus RTU)
3.6.2. Network Address [NETADDR]
The network address of the transmitter.
[Menu path: SETTINGS >↓ RS485 >↓ NETADDR]
3.6.2.1. BACNET
Default: 2
Optional Settings:0 to 127
3.6.2.2. MODBUS
Default: 2
Optional Settings:0 to 247
3.6.3. Baud Rate [NETBAUD]
The baud rate of the network.
[Menu path: SETTINGS >↓ RS485 >↓ NETBAUD]
3.6.3.1. BACNET
Default: 76800 (bps)
Optional Settings: 38400, 19200, 9600