3.5.16.2. H CONFIG=ENTH
Default: Btu/lb [kJ/kg]
Optional Settings: None
3.5.16.3. H CONFIG=DPT
Default: F (°F) [C (°C)]
Optional Settings: None
3.5.17. AO3 Minimum Scale Reading [AO3 MS]
The value that results in an output signal of 0%.
[Menu path: SETTINGS >↓ ANALOG OUT >↓ AO3 MS]
The minimum scale reading is dependent on the RH sensor configuration.
3.5.17.1. H CONFIG=RH
Default: 0 (% RH)
Optional Settings: 0 to 100 (% RH)
3.5.17.2. H CONFIG=ENTH
Default: 0 (Btu/lb) [0 (kJ/kg)]
Optional Settings: -20 to 400 (Btu/lb) [-40 To 800 (kJ/kg)]
3.5.17.3. H CONFIG=DPT
Default: 0 (°F) [0 (°C)]
Optional Settings: -50 to 160 (°F) [-50 to 70 (°C)]
3.5.18. AO3 Full Scale Reading [AO3 FS]
The value that results in an output signal of 100%.
[Menu path: SETTINGS >↓ ANALOG OUT >↓ AO3 MS]
The minimum scale reading is dependent on the RH sensor configuration.
3.5.18.1. H CONFIG=RH
Default: 100 (% RH)
Optional Settings: 0 to 100 (% RH)
3.5.18.2. H CONFIG=ENTH
Default: 200 (Btu/lb) [400 (kJ/kg)]
Optional Settings: -20 to 400 (Btu/lb) [-40 To 800 (kJ/kg)]
3.5.18.3. H CONFIG=DPT
Default: 100 (°F) [50 (°C)]
Optional Settings: -50 to 160 (°F) [-50 to 70 (°C)]
Some B.A.S. application controllers use “span” rather than minimum- and full-scales. The span is
equal to the full-scale – minimum scale and the offset is equal to the minimum scale.